2002-03-26 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110407
 CLUBHOUSE
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- FLORIDA ENERGY CODE 1997 EDITION
 400.0 FLORIDA ENERGY CODE REQUIRES
 ENERGY CODE COMPLIANCE METHOD A WHOLE
 BUILDING, CODE CALCULATIONS INCLUDING
 MANUAL J.
  
 2)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THREE COPIES OF ALL PRODUCT ACCEPTANCE
 TESTING REPORTS SHALL BE REQUIRED FOR
 ALL GLAZED OPENINGS, EXT DOORS,SKYLIGHTS
 GLASS BLOCK, STORM SHUTTERS AS WELL AS
 ROOFING ASSEMBLIES. WHEN REPORTS ARE NOT
 FILED WITH THE PLANS AND THE BUILDING
 IS APPROVED, THE STIPULATION THAT A
 SEPERATE PERMIT WITH ASSOCIATED FEES
 SHALL BE REQUIRED, ALSO THE CITIES
 GUIDE LINES FOR LARGE PROJECTS REGARDING
 PROTECTION FOR ALL GLAZED OPENINGS SHALL
 BE ADHERRED TO, SEE ATTACHED GUIDELINES.
 THE BUILDING OFFICIAL SHALL REVIEW &
 APPROVE ALL PROPOSED ALL PROPOSED PRE-
 STORM PREPERATION PLAN.
  
 3)-THE TRUSS & GIRDER LAYOUT DOES NOT
 INDICATE THE UPLIFT LOADSTO BE RESISTED.
 THEREIS A ANCHOR SCHEDULE INDICATING
 WHAT TYPE OF ANCHOR IS TO BE USED. WITH
 OUT THIS INFORMATION BEFORE THE ISSUANCE
 OF A BUILDING PERMIT THE ARCHETECT AND
 ENGINEER SHALL BE REQUIRED TO REVIEW THE
 TRUSS PLAN LAYOUT WITH THE TRUSS ENGIN-
 EERING CERTIFYING BY AFFIDAVIT THAT THIS
 TRUSS LAYOUT AND ATTACHMENT SHALL ALL
 THE REQUIREMENTS OF THE CODE.
 ANCHOR SSCHEDULE INDICATES:
 H-16 ALLOWABLE @160% 1475 UPL. NOT 1600
 HGT 4 ALLOWABLE @160 9250 UPL NOT 9685
  
 CONTRACTOR TO TRANSPORT PLANS TO COUNTY
 FOR IMPACT FEE ASSESSMENT.
  