Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-02-12 00:00:001) FIRE SPRINKLER PIPING RUN UNDERNEATH
 BUILDING TO MECHANICAL ROOM IS NOT
 PERMITTED. THE PLAN REVIEW RESPONSE
 IS NOT ACCEPTABLE TO THIS OFFICE. NFPA
 24 REQUIRES THAT PRIVATE FIRE SERVICE
 MAINS NOT BE RUN UNDERNEATH BUILDINGS
 EXCEPT WHEN ABSOLUTELY NECESSARY.
 2) FIRE SPRINKLER RISER SIZE COULD NOT
 BE LOCATED ON THE PLANS. PLEASE INDICATE
 ON PLANS RISER SIZE AND UNDERGROUND MAIN
 SIZE.
 3) PLEASE REMOVE 13R REFERENCE FROM PAGE
 F2.61 SINCE IT IS NOT APPLICABLE TO
 THE CLUBHOUSE.
 4) HYDRAULIC CALCULATIONS SUBMITTED
 APPEAR TO BE BUILDING TYPE 1, NOT THE
 CLUBHOUSE.
 5) THIS OFFICE WILL REQUIRE FIRE
 SPRINKLER PROTECTION FOR THE PORCH AREA.
 6) EXIT SIGN LOCATIONS DOES NOT
 CORRELATE WITH OTHER ONES.
 7) PLEASE INCLUDE ALL CHANGES ON THE
 PLAN REVIEW RESPONSES INTO THE DESIGN
 DOCUMENTS.
 8) THIS OFFICE NEEDS CIVIL DRAWINGS
 SUBMITTED TO DETERMINE FIRE MAIN AND
 FIRE HYDRANT LOCATIONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910