Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop E
Sequence Number 2
Notes
Date Text
2002-02-06 00:00:00*****************UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD. PER FS/FAC 471.025
  
 2)NOTE: PLEASE NOTE NO EQUIPMENT GROUND
 TO BE INSTALLED UNTIL AFTER FIRST MEANS
 OF DISCONNECT. (PARALLELING NEUTRAL)
 ALSO SHOWING AN EQUIPMENT GROUNDING
 CONDUCTOR COMING FROM FPL?
  
 3)NOTE: PLEASE CLARIFY CIRCLES ON PLANS
 FOR RISER,,,250VOLT/3 WIRE+NEU/
 DISC SIZE AND SIZE OF FUSES? PLEASE
 CLARIFY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372