| 2002-02-06 00:00:00 | *****************UNSAT *************** | | | | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | BE SIGNED, DATED AND SEALED BY THE | | | ENGINEER OF RECORD. PER FS/FAC 471.025 | | | | | | 2)NOTE: PLEASE NOTE NO EQUIPMENT GROUND | | | TO BE INSTALLED UNTIL AFTER FIRST MEANS | | | OF DISCONNECT. (PARALLELING NEUTRAL) | | | ALSO SHOWING AN EQUIPMENT GROUNDING | | | CONDUCTOR COMING FROM FPL? | | | | | | 3)NOTE: PLEASE CLARIFY CIRCLES ON PLANS | | | FOR RISER,,,250VOLT/3 WIRE+NEU/ | | | DISC SIZE AND SIZE OF FUSES? PLEASE | | | CLARIFY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|