| 2002-02-21 00:00:00 | BUILDING PLAN REVIEW |
| | PLAN REVIEW# 01110407 |
| | CLUBHOUSE |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | |
| | 1)ADDITIONAL INFORMATION REQUIRED, |
| | SOILS REPORT |
| | FL ENERGY CALCS INCLUDING MANUAL J |
| | PRODUCT APPROVAL FOR ALL OPENINGS OF THE |
| | BUILDING ENVELOPE, 3 SETS/ BLDG |
| | MEAN ROOF HEIGTH S1.11INDICATES TO |
| | MEAN ROOF HEIGTHS, SBC 1606.2.4.2 WHERE |
| | MORE THAN ONE LOAD CASE EXISTS, BUILD- |
| | INGS SHALL BE DESIGNED FOR ALL LOAD |
| | CASES. |
| | PRODUCT APPROVALS: 3 COPIES OF PRODUCT T |
| | ESTING REPORTS SBC 1606.2.6.2 FOR ALL |
| | EXTERIOR OPENINGS & ROOFING MATERIALS. |
| | SBCCI OR DADE COUNTY PRODUCT TESTING RE- |
| | PORTS ARE REQUIRED.GABLE END WALL DETAIL |
| | GIVES INFORMATION ON BRACING OF THE |
| | BOTTOM CORD, NO ADDITIONAL INFORMATION |
| | IS GIVEN ON THE 14' VERTICAL MEMBERS OF |
| | THE TRUSS? |
| | TRUSS PLAN S2.62 INDICATES THE UPLIFT |
| | LOADS FOR THE CONNECTORS BUT THERE IS NO |
| | REFRENCE TO THE ACTUAL LOAD CONDITIONS |
| | IMPOSED ON THE TRUSS ITSELF? |
| | PLANS ARE TO BE SUBMITTED TO COUNTY FOR |
| | REVIEW FOR IMPACT FEES. |
| | CITY TO COLLECT FEES FOR RADON FOR STATE |
| | COMPLEX SHALL REQUIRE A RESIDENT INSPEC- |
| | TOR BEFORE ISSUANCE, SEE DON NEELY. |