Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-30 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE PROVIDE CALCULATIONS FOR MIN-
 IMUM FACILITIES USING SPC TABLE 407.
 2) SHT A2.61 PLEASE PROVIDE ELEVATION
 FOR SERVICE BAR SINK. PROVIDE DETAILS
 FOR COMPLIANCE WITH FACBC SEC 4.24.
 3) SHT P2.61 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS TO BE LOCATED CLOSE TO
 FIXTURES IN AN EFFECTIVE RANGE, NOT AT
 TOP OF DROP AS SHOWN.
 4) WATER RISER DIAGRAM DETAILS #4 & #6
 WATER TO EACH RESTROOM TO BE SEPARATE &
 SHUT OFF VALVES ARE REQUIRED FOR EACH
 ROOM. SPC SEC 610.4.1
 5) SHT P4.61 WATER HEATER DETAIL, DIELE-
 CTRIC UNIONS AND REMOTE WATER HEATERS
 NOT APPROVED. CITY CODE SEC 31-29
 6) SHT P4.61 WATER HEATER #3, PLEASE
 PROVIDE DETAILS SHOWING HOW HEATER IS
 READILY ACCESSIBLE PER SPC SEC 501.7
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377