| Plan Review Notes For Permit 01110407 |
| Permit Number |
01110407 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-30 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) PLEASE PROVIDE CALCULATIONS FOR MIN- | | | IMUM FACILITIES USING SPC TABLE 407. | | | 2) SHT A2.61 PLEASE PROVIDE ELEVATION | | | FOR SERVICE BAR SINK. PROVIDE DETAILS | | | FOR COMPLIANCE WITH FACBC SEC 4.24. | | | 3) SHT P2.61 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS TO BE LOCATED CLOSE TO | | | FIXTURES IN AN EFFECTIVE RANGE, NOT AT | | | TOP OF DROP AS SHOWN. | | | 4) WATER RISER DIAGRAM DETAILS #4 & #6 | | | WATER TO EACH RESTROOM TO BE SEPARATE & | | | SHUT OFF VALVES ARE REQUIRED FOR EACH | | | ROOM. SPC SEC 610.4.1 | | | 5) SHT P4.61 WATER HEATER DETAIL, DIELE- | | | CTRIC UNIONS AND REMOTE WATER HEATERS | | | NOT APPROVED. CITY CODE SEC 31-29 | | | 6) SHT P4.61 WATER HEATER #3, PLEASE | | | PROVIDE DETAILS SHOWING HOW HEATER IS | | | READILY ACCESSIBLE PER SPC SEC 501.7 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|