| 2001-12-05 00:00:00 | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | |
| | MECHANICAL ROOM 110 IS INDICATED AS |
| | HAVING FIRE RESISTANCE RATING OF HOUR. |
| | PLEASE IDENTIFY FIRE DAMPERS ON DUCTS |
| | PENETRATING THESE WALLS. |
| | |
| | PLAN SHEET M2.61, INDICATE WHERE AHU |
| | CH-1 IS LOCATED (ABOVE CEILING OR IN A |
| | ROOM).HVAC NOTES ITEM #3, CONDENSATE |
| | DRAIN LINE ROUTE TO FLOOR DRAIN.AS |
| | PER THE COUNTY WIDE AMENDMENTS 1994 |
| | SPC, UNITS LARGER THAN 3 TONS THE |
| | CONDENSATE SHALL TERMINATE. |
| | |
| | 1. INTO AN APPROVED DRYWELL. |
| | 2. CONNECTION AT GROUND FLOOR LEVEL OF |
| | THE STORM DRAINAGE SYSTEM. |
| | |
| | PLEASE NOTE, FAN SHUTDOWN REQUIRED FOR |
| | UNITS WITH CAPACITY OF 2,000 CFM OR |
| | GREATER.WITH NOTIFICATION TO |
| | ALARM/STROBE IN NORMALLY OCCUPIED AREAS. |
| | |
| | |
| | |
| | REVIEW OF THE APARTMENTS - |
| | |
| | 1.EXHAUST FOR THE DRYER VENTS. |
| | NOTE, 25' MAXIMUM LENGTH INCLUDING |
| | A 2 1/2' DEDUCTION FOR EACH 45 AND |
| | A 5' DEDUCTION FOR EACH 90 DEGREE |
| | BEND. |
| | 2.PLEASE INDICATE HOW COMBUSIBLE LINT |
| | IN TO BE REMOVED/CLEANED FROM DUCT. |
| | CLEANOUTS ARE NOT INDICATED ON PLAN. |
| | 3.PROVIDE A DETAIL OF CONDENSATE |
| | TERMINATION LOCATION. |
| | 4.PLANS INDICATE DRYER EXHAUST TO BE |
| | NON-SCREENED WITH A BACK DRAFT |
| | DAMPER.NOTHING IS SPECIFIED FOR |
| | THE TOILET EXHAUST.TOILET EXHAUST |
| | TERMINATION SHALL BE SCREENED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |