Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop M
Sequence Number 1
Notes
Date Text
2001-12-05 00:00:00 
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 MECHANICAL ROOM 110 IS INDICATED AS
 HAVING FIRE RESISTANCE RATING OF HOUR.
 PLEASE IDENTIFY FIRE DAMPERS ON DUCTS
 PENETRATING THESE WALLS.
  
 PLAN SHEET M2.61, INDICATE WHERE AHU
 CH-1 IS LOCATED (ABOVE CEILING OR IN A
 ROOM).HVAC NOTES ITEM #3, CONDENSATE
 DRAIN LINE ROUTE TO FLOOR DRAIN.AS
 PER THE COUNTY WIDE AMENDMENTS 1994
 SPC, UNITS LARGER THAN 3 TONS THE
 CONDENSATE SHALL TERMINATE.
  
 1. INTO AN APPROVED DRYWELL.
 2. CONNECTION AT GROUND FLOOR LEVEL OF
 THE STORM DRAINAGE SYSTEM.
  
 PLEASE NOTE, FAN SHUTDOWN REQUIRED FOR
 UNITS WITH CAPACITY OF 2,000 CFM OR
 GREATER.WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS.
  
  
  
 REVIEW OF THE APARTMENTS -
  
 1.EXHAUST FOR THE DRYER VENTS.
 NOTE, 25' MAXIMUM LENGTH INCLUDING
 A 2 1/2' DEDUCTION FOR EACH 45 AND
 A 5' DEDUCTION FOR EACH 90 DEGREE
 BEND.
 2.PLEASE INDICATE HOW COMBUSIBLE LINT
 IN TO BE REMOVED/CLEANED FROM DUCT.
 CLEANOUTS ARE NOT INDICATED ON PLAN.
 3.PROVIDE A DETAIL OF CONDENSATE
 TERMINATION LOCATION.
 4.PLANS INDICATE DRYER EXHAUST TO BE
 NON-SCREENED WITH A BACK DRAFT
 DAMPER.NOTHING IS SPECIFIED FOR
 THE TOILET EXHAUST.TOILET EXHAUST
 TERMINATION SHALL BE SCREENED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.