| Date |
Text |
| 2001-11-21 00:00:00 | 1) PLEASE BE ADVISED THAT WHEN THIS |
| | PROJECT IS PERMITTED WOULD STIPULATE |
| | THE APPLICABLE FIRE CODE THAT WOULD BE |
| | USED TO REVIEW THE CLUBHOUSE. EFFECTIVE |
| | JANUARY 1, 2002, THE NEW FLORIDA FIRE |
| | PREVENTION CODE WOULD BE APPLICABLE TO |
| | THE CLUBHOUSE WHICH WOULD INVOKE THE |
| | 2000 EDITION OF THE LIFE SAFETY CODE. |
| | PRIOR TO THE ABOVE SUBJECT DATE, THE |
| | 1985 EDITION OF THE LIFE SAFETY CODE |
| | WOULD BE APPLICABLE. |
| | 2) PANIC HARDWARE REQUIRED ON ALL EXIT |
| | DOORS DUE TO OCCUPANCY PROJECTIONS. |
| | 3) PLEASE INDICATE HOW THE MAIN EXIT |
| | IS CAPABLE OF PROVIDING EXITING CAPACITY |
| | FOR AT LEAST 50 PERCENT OF THE PROJECTED |
| | OCCUPANCY LOAD. |
| | 4) BUILDING ADDRESS REQUIRED ON |
| | CLUBHOUSE. |
| | 5) A KNOX-BOX WILL BE REQUIRED FOR FIRE |
| | RESCUE ACCESS. |
| | 6) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS. |
| | 7) OCCUPANT LOAD FOR CLUBHOUSE WILL |
| | BE DETERMINED BY FIRE RESCUE. |
| | 8) FIRE DEPARTMENT CONNECTION IS TO BE |
| | WITHIN 150 FEET OF A FIRE HYDRANT. |
| | 9) NO FIRE HYDRANTS SHOWN ON SITE PLAN. |
| | 10) NO HYDRAULIC CALCULATIONS PROVIDED |
| | WITH PLANS. |
| | 11) WALL POST INDICATOR VALVE SHOWN |
| | BELOW FIRE DEPARTMENT CONNECTION COULD |
| | INTERFERE WITH CONNECTING HOSES TO IT. |
| | 12) UNDERGROUND PIPE RUN UNDERNEATH |
| | THE BUILDING TO MECHANICAL ROOM IS |
| | NOT PERMITTED. |
| | 13) PLEASE EXPLAIN USE OF CHILDREN'S |
| | ROOM. |
| | 14) THE PORCH IF OVER FOUR FEET WIDE AND |
| | COMBUSTIBLE IS REQUIRED TO BE FIRE |
| | SPRINKLER PROTECTED. |
| | 15) IT IS RECOMMENDED THAT DUCT SMOKE |
| | DETECTORS BE INSTALLED IN THE RETURNS |
| | IN UNITS 2000 CFM. |
| | 16) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE FIRE ALARM SYSTEM. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |