Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-11-21 00:00:001) PLEASE BE ADVISED THAT WHEN THIS
 PROJECT IS PERMITTED WOULD STIPULATE
 THE APPLICABLE FIRE CODE THAT WOULD BE
 USED TO REVIEW THE CLUBHOUSE. EFFECTIVE
 JANUARY 1, 2002, THE NEW FLORIDA FIRE
 PREVENTION CODE WOULD BE APPLICABLE TO
 THE CLUBHOUSE WHICH WOULD INVOKE THE
 2000 EDITION OF THE LIFE SAFETY CODE.
 PRIOR TO THE ABOVE SUBJECT DATE, THE
 1985 EDITION OF THE LIFE SAFETY CODE
 WOULD BE APPLICABLE.
 2) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS DUE TO OCCUPANCY PROJECTIONS.
 3) PLEASE INDICATE HOW THE MAIN EXIT
 IS CAPABLE OF PROVIDING EXITING CAPACITY
 FOR AT LEAST 50 PERCENT OF THE PROJECTED
 OCCUPANCY LOAD.
 4) BUILDING ADDRESS REQUIRED ON
 CLUBHOUSE.
 5) A KNOX-BOX WILL BE REQUIRED FOR FIRE
 RESCUE ACCESS.
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 7) OCCUPANT LOAD FOR CLUBHOUSE WILL
 BE DETERMINED BY FIRE RESCUE.
 8) FIRE DEPARTMENT CONNECTION IS TO BE
 WITHIN 150 FEET OF A FIRE HYDRANT.
 9) NO FIRE HYDRANTS SHOWN ON SITE PLAN.
 10) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH PLANS.
 11) WALL POST INDICATOR VALVE SHOWN
 BELOW FIRE DEPARTMENT CONNECTION COULD
 INTERFERE WITH CONNECTING HOSES TO IT.
 12) UNDERGROUND PIPE RUN UNDERNEATH
 THE BUILDING TO MECHANICAL ROOM IS
 NOT PERMITTED.
 13) PLEASE EXPLAIN USE OF CHILDREN'S
 ROOM.
 14) THE PORCH IF OVER FOUR FEET WIDE AND
 COMBUSTIBLE IS REQUIRED TO BE FIRE
 SPRINKLER PROTECTED.
 15) IT IS RECOMMENDED THAT DUCT SMOKE
 DETECTORS BE INSTALLED IN THE RETURNS
 IN UNITS 2000 CFM.
 16) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910