Plan Review Notes
Plan Review Notes For Permit 01110407
Permit Number 01110407
Review Stop B
Sequence Number 1
Notes
Date Text
2001-12-08 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01110409
 ADDRESS TO BE DETERMINED
 VILLAGE WEST LUXUARY APARTMENTS
 PARCEL "D" PHASE I
 CLUBHOUSE
 OWN: EPOCH PROPERTIES
 TEL: ( 407) 644-9055
 FAX: (407)644-9845
  
  
 PLAN REVIEW WILL BE COMPLETED UNDER THE
 1997 STANDARD BUILDING CODE.
  
 CLUBHOUSE:
 ASSEMBLY A-2
 TYPE V UNPROTECTED, FULLY SPRINKLERED
 AREA 12,453
  
 CS1.01 INDICATES THE ABOVE INFORMATION,
 "FULLY SPRINKLERED" SBC TABLE 500
 FOOTNOTE "J" BUILDINGS ARE TO BE FULLY
 SPRINKLERED IN ACCORDANCE WITH THE
 STANDARDS LISTED IN 903.2 FOR ALLOWABLE
 AREA INCREASES. SHEET F2.61 INDICATES
 THE USE OF NFPA 13-R. THIS IA NOT
 ACCEPTIBLE SEE SBC903.2 AUTOMATIC
 FIRE SPRINKLER SYSTEMS PERMITTED BY
 THIS CODE SHALL COMPLY WITH NFPA 13.
  
 ADDITIONAL INFORMATION REQUIRED:
 SOILS REPORT
 FL. ENERGY CALS & WORKSHEETS.
 PRODUCT APPROVAL AS STATED UNDER
 SITE AMENITIES.
  
 FAIR HOUSING: SHEET AO.61 CLOSET 104
 DOESN'T MEET 18" ACCESS AT LATCH SIDE OF
 THE DOOR.
 MAIL BOXES: A5.63 DETAIL 3 TO COMPLY
 WITH ANSI 117.1 (308) REACH RANGES
 AADAAG COEFICIENT OF SLIP RESISTANCE
 FOR ACCESSIBLE AREAS (FLOORS) 0.6
 AND 0.8 FOR RAMPS.
  
 MEAN ROOF HEIGTH NOT GIVEN. ALSO THE
 PRESSURES EXERTED ON ALL OPENINGS DOORS
 AND WINDOWS, PLEASE INDICATE ON ELEVA-
 TIONS.
  
 PRODUCT APPROVALS: FRONT ENTRY IS INDICA
 TING A FRENCH DOOR, SIDELITES & TRANSOM.
 THE PRODUCT TESTED NEEDS TO SHOW THIS
 CONFIGURATION OR TESTING OF MULLIONS
 CULMINATING WITH THIS CONFIGURATION.
  
 DISCREPANCY SHEET A5.65 DETAIL #2 INDICA
 TES A FRAME WALL & COLUMNS VS. S2.62
 GIRDER GT, ADDITIONAL INFORMATION
 REQUIRED.
  
 DISCREPANCY SHEET A5.62 REAR ELEVATION
 WORKOUT ROOM 84'-0" IS THE SAME AS THE
 FLOOR PLAN, VS 81' ON THE ROOF PLAN.
  
 A GABLE WALL SECTION DETAIL FOR THE WALL
 OF THE WORK OUT ROOM SHALL BE REQUESTED.
 ADDITIONAL INFOR. THIS GABLE TRUSS IS
 14' VERTICALLY, WHAT TYPE OF REINFORCE-
 MENT SHALL BE REQUIRED? OR IS THIS TO
 BE A RAKE BEAM?
 SHEET S3.12 DETAIL #3 SIMPSON HGAM (10)
 SEE FOOTNOTE (2) MANUFAC. SPEC CATALOG
 TRUSS TO BE A MINIMUM OF 21/2 " THICK.
 WHAT TYPE OF ANCHOR IS TO BE USED IN
 THIS APPLICATION?
  
 GLAZED FIXED PANELS NEXT TO SWING DOORS
 A HAZARDOUS LOCATION SBC 2405.2.1(4)
  
 SHEET S2.61 FOOTER (TS1) INDICATES A
 BEARING WALL BETWEEN THE EXERCISE ROOM
 AND HALL 120A/ RESTROOM 121. S2.62 NOTE
 12 ALSO INDICATES A BEARING WALL, THERE
 IS NO INFO. ON A HEADER OR GIRDER TO
 PICK UP LOAD WHERE WALL ENDS. TI/ T2
 ARE A SPLIT TRUSS WILL THEY BEAR ON THIS
 WALL?
  
 TRUSS PLAN MISSING THE LOADS TO BE
 RESISTED, VERTICAL, HORIZONTAL & GRAVITY
 COORALTE WITH ANCHOR SCHEDULE.
  
 PLANS ARE TO BE SUBMITTED TO THE
 COUNTY BUILDING DEPART FOR ASSESMENT OF
 COUNTY IMPACT FEES BEFORE ISSUANCE
 OF A BUILDING PERMIT.
  
 STATE RADON FEES COLLECTED BY THE CITY.
  
 COMPLEX WILL REQUIRE A RESIDENT INSPECT-
 OR CONTACT DON NEELY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412