Plan Review Notes
Plan Review Notes For Permit 01110401
Permit Number 01110401
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-12-11 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 ON PLANS. SHOULD READ 1985 EDITION
 INSTEAD OF 1997 EDITION.
 2) PLEASE INDICATE HOW FIRE RESCUE
 ACCESS IS ACCOMPLISHED THRU THE
 RELOCATED FENCE AND GATES.
 3) THE BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. TYPE VI CONSTRUCTION IS
 NOT PERMITTED IN THE CITY FIRE LIMITS.
 PLEASE SEE APPENDIX F OF THE STANDARD
 BUILDING CODE AND CHAPTER 11 OF THE
 CITY CODE.
 4) WRONG INFORMATION REGARDING BUILDING
 CODE INFORMATION. BROWARD COUNTY
 EDITION REFERENCED ON PLANS IS
 INCORRECT.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 6) PLEASE INDICATE WHAT SAFETY MEASURES
 WILL BE TAKEN FOR THE DISPLAY OF
 VEHICLES.
 7) PLEASE IDENTIFY EXIT AISLES IN THE
 MINI SHOWROOM SO PERSONS CAN REACH THE
 EXIT DOORS ON THE NEW ADDITION.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF FIRE SPRINKLER
 SYSTEM.
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW FIRE ALARM EQUIPMENT SHOWN
 ON THE PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910