| Plan Review Notes For Permit 01110401 |
| Permit Number |
01110401 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-11 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | ON PLANS. SHOULD READ 1985 EDITION | | | INSTEAD OF 1997 EDITION. | | | 2) PLEASE INDICATE HOW FIRE RESCUE | | | ACCESS IS ACCOMPLISHED THRU THE | | | RELOCATED FENCE AND GATES. | | | 3) THE BUILDING IS LOCATED IN THE CITY | | | FIRE LIMITS. TYPE VI CONSTRUCTION IS | | | NOT PERMITTED IN THE CITY FIRE LIMITS. | | | PLEASE SEE APPENDIX F OF THE STANDARD | | | BUILDING CODE AND CHAPTER 11 OF THE | | | CITY CODE. | | | 4) WRONG INFORMATION REGARDING BUILDING | | | CODE INFORMATION. BROWARD COUNTY | | | EDITION REFERENCED ON PLANS IS | | | INCORRECT. | | | 5) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 6) PLEASE INDICATE WHAT SAFETY MEASURES | | | WILL BE TAKEN FOR THE DISPLAY OF | | | VEHICLES. | | | 7) PLEASE IDENTIFY EXIT AISLES IN THE | | | MINI SHOWROOM SO PERSONS CAN REACH THE | | | EXIT DOORS ON THE NEW ADDITION. | | | 8) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF FIRE SPRINKLER | | | SYSTEM. | | | 9) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR NEW FIRE ALARM EQUIPMENT SHOWN | | | ON THE PLANS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|