| Date |
Text |
| 2001-12-12 00:00:00 | THE PRIMARY USE OF THIS BUILDING AS |
| | DESCRIBED IN SBC 310 IS MERCANTILE.AS |
| | SUCH IT APPEARS TO EXCEED THE AREA |
| | ALLOWED BY SBC TABLE 500 FOR A TWO |
| | STORY TYPE IV, FS BUILDING.(27 KSF) |
| | |
| | FURTHER, THE SERVICE PORTIONS, GROUP |
| | "S"FOR THE SAME CONSTRUCTION TYPE IS 48 |
| | KSFWITH THE AREA INCREASES ALLOWED BY |
| | SBC 503 APPLIED. |
| | |
| | PLEASE PROIDE A RECENT PROPERTY SURVEY, |
| | ONE YEAR OR LESS OLD. |
| | |
| | INDICATE ON THE SITE PLAN THE LOCATION |
| | OF ANY FIRE WALLS.(SEE SBC 202 "FIRE |
| | WALL") |
| | |
| | IS THE SPRINKLER A SINGLE RISER SYSTEM? |
| | PLEASE PROVIDE AN ENGINEER'S ANALYSIS |
| | OF THE SYSTEM FOR THE ENTIRE BUILDING |
| | SO THAT COMPLIANCE WITH SECTION 4-2.1 |
| | OF NFPA 13-96 MAY BE DETERMINED. |
| | |
| | SHEET A4 SECTION 2/A4 CALLS OUT THE USE |
| | OF PLYWOOD WHICH IS NOT PERMITTED IN |
| | TYPE IV CONSTRUCTION, SEE SBC 606 AND |
| | SBC APPENDIX F 102.2.7. |
| | |
| | SHEET S1, SECTION C, WHAT IS THE SPACING |
| | OF THE L3X3X1/4 ? |
| | |
| | SHEET S2 CITES THE SFBC, PLEASE REVISE |
| | TO INCLUDE, AND ASCERTAIN COMPLIANCE |
| | WITH, THE 1997 SBC. |
| | |
| | PLEASE PROVIDE THE TESTING AND OR |
| | NNOTICE OF ACCEPTANCE REPORTS FOR THE |
| | DOORS, WINDOWS AND ROOF COVERINGS. |
| | ALSO, INDICATE HOW THE GLAZED PORTIONS |
| | OF THE ADDITION WILL RESIST HURRICANE |
| | MISSILE IMPACT.DESIGNATE THE LOADS ON |
| | THE PLANS FOR THE ABOVE MENTIONED ITEMS. |
| | |
| | SHEET A2, SHOW THE CALCULATIONS FOR THE |
| | SIZING OF THE ROOF EMERGENCY OVERFLOW |
| | SCUPPER IN ACCORDANCE WITH SECTION 1109 |
| | OF THE 1994 STANDARD PLUMBING CODE. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO THE |
| | COUNTY FOR THE CITY, THE PERMIT PLANS |
| | STAMPED BY THAT OFFICE, AND ACOPY OF |
| | THE RECEIPT ATTACHE TO THE PERMIT |
| | APPLICATION. |