2001-12-12 00:00:00THE PRIMARY USE OF THIS BUILDING AS
 DESCRIBED IN SBC 310 IS MERCANTILE.AS
 SUCH IT APPEARS TO EXCEED THE AREA
 ALLOWED BY SBC TABLE 500 FOR A TWO
 STORY TYPE IV, FS BUILDING.(27 KSF)
  
 FURTHER, THE SERVICE PORTIONS, GROUP
 "S"FOR THE SAME CONSTRUCTION TYPE IS 48
 KSFWITH THE AREA INCREASES ALLOWED BY
 SBC 503 APPLIED.
  
 PLEASE PROIDE A RECENT PROPERTY SURVEY,
 ONE YEAR OR LESS OLD.
  
 INDICATE ON THE SITE PLAN THE LOCATION
 OF ANY FIRE WALLS.(SEE SBC 202 "FIRE
 WALL")
  
 IS THE SPRINKLER A SINGLE RISER SYSTEM?
 PLEASE PROVIDE AN ENGINEER'S ANALYSIS
 OF THE SYSTEM FOR THE ENTIRE BUILDING
 SO THAT COMPLIANCE WITH SECTION 4-2.1
 OF NFPA 13-96 MAY BE DETERMINED.
  
 SHEET A4 SECTION 2/A4 CALLS OUT THE USE
 OF PLYWOOD WHICH IS NOT PERMITTED IN
 TYPE IV CONSTRUCTION, SEE SBC 606 AND
 SBC APPENDIX F 102.2.7.
  
 SHEET S1, SECTION C, WHAT IS THE SPACING
 OF THE L3X3X1/4 ?
  
 SHEET S2 CITES THE SFBC, PLEASE REVISE
 TO INCLUDE, AND ASCERTAIN COMPLIANCE
 WITH, THE 1997 SBC.
  
 PLEASE PROVIDE THE TESTING AND OR
 NNOTICE OF ACCEPTANCE REPORTS FOR THE
 DOORS, WINDOWS AND ROOF COVERINGS.
 ALSO, INDICATE HOW THE GLAZED PORTIONS
 OF THE ADDITION WILL RESIST HURRICANE
 MISSILE IMPACT.DESIGNATE THE LOADS ON
 THE PLANS FOR THE ABOVE MENTIONED ITEMS.
  
 SHEET A2, SHOW THE CALCULATIONS FOR THE
 SIZING OF THE ROOF EMERGENCY OVERFLOW
 SCUPPER IN ACCORDANCE WITH SECTION 1109
 OF THE 1994 STANDARD PLUMBING CODE.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY FOR THE CITY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE, AND ACOPY OF
 THE RECEIPT ATTACHE TO THE PERMIT
 APPLICATION.