| Plan Review Notes For Permit 01110376 |
| Permit Number |
01110376 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-27 00:00:00 | *******************PROVISO************** | | | | | | | | | 1.PLAN SHEET M-1, EXISTING CORRIDOR | | | INDICATES TO DAMPERS IN A FIRE | | | RATED WALL. DAMPERS ARE NOT SHALL BE | | | IDENTIFIED AS FIRE DAMPERS. | | | | | | 2.PLANS DO NOT PROVIDE INSTALLATION | | | DETAILS FOR FIRE DAMPERS.FIRE | | | DAMPERS SHALL COMPLY WITH THE | | | REQUIREMENTS OF UL 555 AND SHALL | | | BEAR THE LABEL OF AN APPROVED | | | TESTING AGENCY AS PER 1997 SMC | | | 610.1.1. | | | | | | 3.PLANS TO DO INDICATE MATERIAL OF | | | PIPING FOR CONDENSER WATER.PLEASE | | | NOTE SHOULD COPPER PIPE BE INSTALLED | | | IT SHALL BE BRAZED AS PER 1997 SMC | | | TABLE 1205. | | | | | | 4.PLAN SHEET M-2 AND M-3 CONTRADICT | | | TERMINATION OF EMERGENCY DRAIN FOR | | | AUXILIRY DRAIN PAN.EMERGENCY DRAIN | | | LINE SHALL NOT TERMINATE TO RISER AS | | | INDICATED ON PLAN SHEET M-3.DRAIN | | | SHALL COMPLY WITH 1997 SMC 304.8.6.1 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|