2001-11-27 00:00:00*******************PROVISO**************
  
  
 1.PLAN SHEET M-1, EXISTING CORRIDOR
 INDICATES TO DAMPERS IN A FIRE
 RATED WALL. DAMPERS ARE NOT SHALL BE
 IDENTIFIED AS FIRE DAMPERS.
  
 2.PLANS DO NOT PROVIDE INSTALLATION
 DETAILS FOR FIRE DAMPERS.FIRE
 DAMPERS SHALL COMPLY WITH THE
 REQUIREMENTS OF UL 555 AND SHALL
 BEAR THE LABEL OF AN APPROVED
 TESTING AGENCY AS PER 1997 SMC
 610.1.1.
  
 3.PLANS TO DO INDICATE MATERIAL OF
 PIPING FOR CONDENSER WATER.PLEASE
 NOTE SHOULD COPPER PIPE BE INSTALLED
 IT SHALL BE BRAZED AS PER 1997 SMC
 TABLE 1205.
  
 4.PLAN SHEET M-2 AND M-3 CONTRADICT
 TERMINATION OF EMERGENCY DRAIN FOR
 AUXILIRY DRAIN PAN.EMERGENCY DRAIN
 LINE SHALL NOT TERMINATE TO RISER AS
 INDICATED ON PLAN SHEET M-3.DRAIN
 SHALL COMPLY WITH 1997 SMC 304.8.6.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE