| Plan Review Notes For Permit 01110339 |
| Permit Number |
01110339 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-02-28 00:00:00 | | | | *******************UNSAT!*************** | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | AND RESUBMIT FOR REVIEW. | | | | | | 1) WATTAGE OF FIXTURES.(HIGH VOLTAGE OR | | | LOW VOLTAGE?) | | | | | | 2) CONDUIT & WIRE SIZE AND TYPE. | | | | | | 3) SIZE OF OVERCURRENT PROTECTION. | | | | | | 4) NUMBER OF CIRCUITS FEEDING FIXTURES A | | | ND CIRCUIT NUMBERS. | | | | | | 5) THE PLANS HAVE A TITLE BLOCK WITH NO | | | SEAL. PLEASE COMPLY WITH 481-2.2.1.(FS/F | | | AC.) | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|