| 2002-03-08 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 12/14/01: |
| | |
| | 10) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | REFER TO BUILDING PLAN REVIEW12/14/01 |
| | |
| | 11) --PROVISO-- |
| | SBC 2308.3.2THE WINDOW HEADERS SHALL |
| | BE SUPPORTED BY JACK STUDS IN ACCORDANCE |
| | WITH TABLE 2308.3A |
| | |
| | 13) --PROVISO-- |
| | SBC* 104.1.1NO ROOF COVERING SPECIFIED |
| | A ROOFING PERMIT APPLICATION IS REQUIRED |
| | |
| | 22) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SBC 1608.2SECTION 4/S1.SHOW/STATE |
| | THE MEANS OF FIXING THE 2X4 TO THE 2X6. |
| | |
| | 37) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FL ENERGY CODE 101.1.2THE ADDITION |
| | SHALL COMPLY WITH FLORIDA ENERGY CODE. |
| | |
| | 38) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FL ENERGY CODE 103.0COMPLIANCE SHALL |
| | BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |