| 2002-02-04 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 12/14/01: |
| | |
| | 1) CHANGE OF USE FROM RESIDENTIAL TO |
| | BUSINESS. IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY, PLANS STAMPED BY THEM |
| | AND COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 7) **PROVISO**THIS PERMIT APPLICATION |
| | SHOWS A WOOD FLOOR WHILST FOUNDATION |
| | PERMIT# 01081206 SHOWS A CONCRETE SLAB. |
| | UNDERFLOOR VENTILATION OF EXISTING |
| | BUILDING MUST BE MAINTAINED (SBC 2304.3) |
| | |
| | 10) THE RESUBMITTAL DOES NOT ADDRESS |
| | THIS REVIEW COMMENT. |
| | |
| | 11) THE RESUBMITTAL DOES NOT ADDRESS |
| | THIS REVIEW COMMENT. |
| | |
| | 13) **PROVISO** |
| | SBC* 104.1.1A SEPARATE ROOFING PERMIT |
| | APPLICATION IS REQUIRED. |
| | |
| | 16) **PROVISO** |
| | SBC 1013.6THE REVISED PLANS SHOW THE |
| | REQUIRED 12" HANDRAIL EXTENSION AT THE |
| | BOTTOM OF THE RAMP BUT NOT AT THE TOP OF |
| | THE SLOPED SECTION. |
| | |
| | 17) SBC 1013.6THE HEIGHT OF THE RAMP |
| | HANDRAIL IS STILL SHOWN ON SECTION 1/S1 |
| | AS 26".AMEND THE HEIGHT TO BETWEEN 34" |
| | AND 38". |
| | |
| | 19) FL ACC CODE 4.9.4(2)SECTION 11/S1 |
| | SHOWS THE CORRECT REQUIREMENT FOR THE |
| | STAIRCASE HANDRAILS TO CONTINUE TO SLOPE |
| | PAST THE BOTTOM RISER BY A DISTANCE |
| | EQUAL TO THE DEPTH OF ONE TREAD AND THEN |
| | EXTEND HORIZONTALLY FOR A FURTHER 12". |
| | SECTION 7/S1 DOES NOT REFLECT THIS AND |
| | SHOULD ME AMENDED TO AVOID CONFUSION. |
| | |
| | 22) THE RESUBMITTAL DOES NOT ADDRESS |
| | THIS REVIEW COMMENT. |
| | |
| | 28) **PROVISO**THE PLAN ON SHEET S1 |
| | CORRECTLY STATES THAT THE FLOOR LEVEL OF |
| | THE ADDITION IS TO MATCH THAT OF THE |
| | EXISTING BUILDING.THE STEPS SHOWN ON |
| | SHEET S2 'FULL HEIGHT WALL SECTION' |
| | SHOULD BE DELETED TO REFLECT THIS AND |
| | AVOID CONFUSION. |
| | |
| | 37) FL ENERGY CODE 101.1.2THE ADDITION |
| | SHALL COMPLY WITH FLORIDA ENERGY CODE. |
| | |
| | 38) FL ENERGY CODE 103.0COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |