| Plan Review Notes For Permit 01110271 |
| Permit Number |
01110271 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-26 00:00:00 | ON 12.24.01 WRITER CONTACTED BRIAN | | | BURCHARD BY TELEPHONE TO DISCUSS FIRE | | | ALARM SYSTEM ISSUES. HE WAS ADVISED THAT | | | AN ALERT TONE OF 3-10 SECONDS FOLLOWED | | | BY A MESSAGE REPEATED AT LEAST THREE | | | TIMES TO INFORM THE OCCUPANTS MUST BE | | | PROVIDED. HE WAS FURTHER ADVISED THAT | | | NO INFORMATION WAS PROVIDED WITH | | | REGARDS TO WHAT THE VOICE EVACUATION | | | MESSAGE WILL SAY. ALSO HE WAS ADVISED | | | THAT THE LOCATION OF THE REMOTE FIRE | | | ALARM PANEL APPEARS TO HAVE BEEN | | | RELOCATED. HE WAS ADVISED THAT THE | | | REMOTE FIRE ALARM PANEL AND THE | | | MAIN FIRE CONTROL PANEL ARE TO BE | | | INSTALLED IN AREAS WITH AT LEAST A | | | ONE HOUR FIRE RESISTANCE RATING AND HAVE | | | AT LEAST THREE FEET OF CLEARANCE. WIRING | | | FOR THE TWO MUST BE NO FARTHER APART | | | THAN 100 FEET OR BE ENCLOSED IN A TWO | | | HOUR RATED ENCLOSURE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|