| Plan Review Notes For Permit 01110271 |
| Permit Number |
01110271 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-13 00:00:00 | 1) NO CUT SHEETS PROVIDED FOR NEW FIRE | | | ALARM SYSTEM. | | | 2) THE FIRE ALARM SYSTEM SHOULD BE | | | VOICE EVACUATION. PLEASE INDICATE WHAT | | | THE TAPED MESSAGE PORTION OF THE FIRE | | | ALARM SYSTEM WILL SAY. | | | 3) PLEASE INDICATE ON PLANS THAT THE | | | VALVES ON THE BACKFLOW DEVICE WILL | | | BE SUPERVISED. | | | 4) FIRE ALARM SYSTEM TO BE MONITORED | | | BY A LICENSED UL LISTED CENTRAL STATION | | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|