Plan Review Notes
Plan Review Notes For Permit 01110260
Permit Number 01110260
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-16 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE A2, ELEVATION #1. HEIGHT OF W/C
 TO BE 17" TO 19" PER FACBC SEC 4.16.3
 NOT 1'3" AS SHOWN.
  
 2) PAGE A2, ELEVATION #1. CONTROLS FOR
 FLUSH VALVE ON W/C TO BE ON WIDE SIDE AS
 PER FACBC SEC 4.16.5 NOT AS SHOWN ON
 WALL SIDE.
  
 3) PAGE A2, ELEVATIONS #1 & #4. LAVS TO
 COMPLY WITH FACBC SEC 4.19.4. HOT WATER
 AND DRAIN PIPES UNDER LAVS SHALL BE IN-
 SULATED ECT.
  