Plan Review Notes For Permit 01110257
Permit Number 01110257
Review Stop E
Sequence Number 1
Notes
Date Text
2001-11-28 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 COMING IN AS FIRE ALARM PERMIT AND
 SCOPE OF WORK/PLANS INCLUDE ELECTRICAL?
 PLEASE NOTE THAT PLANS SHOW MUCH MORE
 WORK THAN WHATS ON APPLICATION.
 PLEASE SUBMIT CONTRACT TO VERIFY VALUE
 PER 104.7.5 OF COUNTY/CITY WIDE ADMIN
 CODE.
  
 2)NOTE: PLEASE NOTE PLANS SHOW NEW PANEL
 "C" BUT NO DETAIL FOR PANEL? WIRE, FEED,
 ETC ETC.
  
 3)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 TO CORRELATE WITH ALL NEW CIRCUITS ADDED
 TO PLANS.
  
 4)NOTE: PERMIT APPLICATION SHOWS NEW
 DATA/VOICE? PLEASE CLARIFY ALL LOCATIONS
 ON PLANS.
  
 5)NOTE:" PLEASE NOTE FIRE ALARM TO BE
 PERMITTED SEPARATELY.
  
 6)NOTE: PLEASE CLARIFY IF EXISTING
 SIGN CIRTCUIT MEETS 600-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372