| Plan Review Notes For Permit 01110232 |
| Permit Number |
01110232 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE 2 OF 14, BACKFLOW TO BE RELOCAT- | | | ED, PERMIT REQUIRED AND UTILITY DEPT. TO | | | APPROVE LOCATION. | | | 2) PAGE 2 OF 14, DETAIL OF PROPOSED | | | WATER SERVICE SHOWS (2) 1" PVC SERVICE | | | LINES TO DRINKING FOUNTAINS. HOW MANY | | | DRINKING FOUNTAINS ARE THERE? | | | 3) PAGE W OF 14, HIGH-LOW DRINKING FOUN- | | | TAINS ARE REQUIRED TO COMPLY WITH FACBC | | | SEC 4.15.2 AND SEC 4.1.3(10) PROVISIONS | | | FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. | | | 4) IRRIGATION SHOP DRAWING, RAIN SENSOR | | | REQUIRED FOR CONTROL PANEL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|