2001-12-11 00:00:00 
 PLEASE CLARIFY THE FOLLOWING
 DISCREPANCY:
  
 PLAN SHEET 2 OF 2, BUILDING SECTION I
 INDICATES GREASE DUCT WITH 1" SLOPE
 BACK TO THE HOOD.BUILDING SECTION 2
 INDICATES THE GREASE DUCT WITH THE
 SLOPE TOWARDS THE SHAFT, AWAY FROM THE
 HOOD.
  
 PLEASE NOTE 1" PER FOOT TOWARD THE HOOD,
 AS PER 1997 SMC 505.4.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.