2001-11-13 00:00:00*******************DENIED***************
  
 1.HOOD AIR VELOCITY FOR HOOD #1 IS
 1,440 FPM, AS PER 1997 SMC 505.7,
 AIR VELOCITY WITHIN THE DUCT SYSTEM
 SHALL NOT BE LESS OF 1,500 FPM.
  
 2.SHAFTS THAT CONSTITUTE AIR DUCTS OR
 THAT ENCLOSE AIR DUCTS USED FOR THE
 MOVEMENT OF ENVIRONMENTAL AIR SHALL
 NOT ENCLOSE
  
 (A) EXHAUST DUCTS USED FOR THE
 REMOVAL OF GREASE-LADEN VAPORS
 FROM COOKING EQUIPMENT
  
 3.FIRE DAMPERS SHALL BE INSTALLED
 WHERE DUCTS PENETRATE SHAFT WALLS
 HAVING A FIRE RESISTANCE RATING OF
 1 HOUR OR MORE.1997 SMC 610.1.2,
 #2.
  
 PLEASE NOTE - EXHAUST OUTLET FOR DUCTS
 CONVEYING NOXIOUS GASES, FLAMMALBE
 VAPORS, AND DUCTS SERVING COMMERICAL
 FOOD COOKING AND PROCESSING EQUIPMENT
 SHALL TERMINATE 10 FT FROM ANY ADJACENT
 BUILDING, PARKING AREA, PROPERTY LINE,
 WINDOW, DOOR OR AIR INTAKE.
  