2002-02-14 00:00:00SECOND CHECKLIST:
  
  
 1-RESUBMITTED DRAWINGS ARE THE SAME THAT
 WERE ORIGINALLY SUBMITTED.SOME CHANGES
 WERE DONE USING WHITEOUT & INFORMATION
 REQUESTED WAS NOT GIVEN AND/OR NOT
 PROPERLY ADDRESSED.
 SEE PREVIOUS CHECKLIST.
 2-SOIL TEST REPORT CALLS FOR DEMUCKING.
 PROVIDE SPECIFICATIONS FOR DEMUCKING
 AND ENGINEERING SHORING DETAILS AND
 SPECS TO PROTECT EXISTING STRUCTURE.
 3-PROVIDE COMPLETE WALL SECTION/DETAIL
 SHOWING NEW WALL BETWEEN EXISTING
 KITCHEN AND NEW FAMILY ROOM.
 -SHOW HOW ARE NEW TRUSSES SUPPORTED.
 -WHAT GOING TO BE DONE ABOUT EXISTING
 OVERHANG.
 -HOW ARE NEW TRUSSES GOING TO BE
 SUPPORTED ON EXISTING ROOF.
 -HOW ARE EXISTING TRUSSES GOING TO BE
 SUPPORTED WHEN EXISTING BEARING WALL
 IS GOING TO BE REMOVED?
 -PROVIDE SHORING DETAILS AND SPECS.
 4-DRAW FLOOR PLAN TO A LARGER SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO SHOW
 ALL WALLS, COLUMNS, OPENING DIMENSIONS
 ETC. (SEC. 104.2.1 CITY AMENDMENTS).
 5-SEE PLANS FOR ADDITIONAL COMMENTS AND
 PLEASE BRING BACK REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 6-RESUBMITTAL FEES WILL BE CHARGED.
 7-SOIL TEST REPORT NEED TO HAVE ORIGINAL
 SIGNATURE, SEAL AND DATE BY THE
 PROFESSIONAL ENGINEER WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 8-PROVIDE PRODUCT APPROVAL FOR:
 A)EXTERIOR REAR DOOR W/ COMPLETE PRODUCT
 APPROVAL REPORT ND MATCHING DRAWINGS.
 B)WINDOW MULLIONS.