Plan Review Notes
Plan Review Notes For Permit 01110119
Permit Number 01110119
Review Stop M
Sequence Number 1
Notes
Date Text
2001-11-16 00:00:00*******************DENIED***************
  
  
 PLEASE CLARIFY CHANGE OUT OF 2 1/2 TON
 SYSTEM TO A 3 1/2 TON SYSTEM.PLAN
 REFLECTS A 450 CFM AIR DISTRIBUTION.A
 3 1/2 TON SYSTEM HAS THE CAPACITY FOR
 1800 CFM.UNIT IS TO LARGE FOR WHAT
 PLAN INDICATES IS BEING UTILIZED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS 659-8096
 EXT. 8388.