| Plan Review Notes For Permit 01110119 |
| Permit Number |
01110119 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-16 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE CLARIFY CHANGE OUT OF 2 1/2 TON | | | SYSTEM TO A 3 1/2 TON SYSTEM.PLAN | | | REFLECTS A 450 CFM AIR DISTRIBUTION.A | | | 3 1/2 TON SYSTEM HAS THE CAPACITY FOR | | | 1800 CFM.UNIT IS TO LARGE FOR WHAT | | | PLAN INDICATES IS BEING UTILIZED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS 659-8096 | | | EXT. 8388. |
|