| 2001-11-19 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTETHAT ALL SHEETS |
| | MUST CONTAIN A TITLE BLOCK FOR THE |
| | ENGINEER OF RECORD. PER 61G15-23.002 |
| | |
| | 2)NOTE: PLEASE NOTE MISSING EGRESS |
| | LIGHTING PER 210-70 LEAVING FAMILY ROOM |
| | TO OUTSIDE. |
| | |
| | 3)NOTE: PLEASE NOTE MISSING GFI OUTLET |
| | FOR BATHROOM. 210-52D, 210-8 |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5)NOTE: PLEASE SUBMIT COMPLET LOAD |
| | CALCULATIONS FOR SERVICE. 220-3-C-1 |
| | |
| | 6)NOTE: PLEASE NOTE THAT SERVICE IS |
| | SHOWN AS EXSITING 150A PANEL AND 200AMP |
| | OCP? PLEASE CLARIFY SERVICE. |
| | |
| | 7)NOTE: PLEASE ALSO NOTE THAT PARTIAL |
| | PANEL SCHEDULE SUBMITTED REFERENCES |
| | 150V FOR CIRCUITS?? PLEASE NOTE THAT |
| | THIS DOES NOT CORRELATE WITH ANY VOLTAGE |
| | -S THAT MAY BE COMMON ON SFR?? |
| | |
| | 8)NOTE: PLEASE CLARFIY IF EQUIPMENT ON |
| | RISER DIAGRAM IS NEW? |
| | IF SO, PLEASE SUBMIT AIC RATINGS FOR |
| | ANY NEW EQUIPMENT PER 110-9/215-5. |
| | |
| | 9) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | NEW FOOTER STEEL TO BE INCLUDED. |
| | |
| | 10)NOTE: PLEASE NOTE THAT ELECTRICAL |
| | PLANS ARE TO INCLUDE ANY A/C EQUIPMENT |
| | BEING INSTALLED. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |