| 2001-12-10 00:00:00 | CHECKLIST: |
| | 1-FOUNDATION PLAN AND FLOOR PLAN DON'T |
| | MATCH. CLEARLY SHOW THE BEARING WALL |
| | AND OR COLUMNS REQUIRED TO SUPPORT |
| | EXISTING AND PROPOSED ROOF. |
| | -CLEARLY SPECIFY PROVISIONS TAKEN TO |
| | REINFORCE AREAS FOR NEW OPENINGS ON |
| | EXISTING BEARING WALL. SPECIFY BEAMS. |
| | 2-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS AND SEC. 2405.2 SBC 1997. |
| | 3-FILL IN DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM ATTACHED |
| | 4-PROVIDE ATTIC ACCESS AT NEW ROOF AREA. |
| | SECTION 2309.6 SBC 1997. |
| | 5-PROVIDE COMPLETE STRUCTURAL BUCK |
| | DETAILS FOR EXTERIOR DOORS AND WINDOWS |
| | SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 |
| | 6-PROVIDE COMPLETE AND CLEAR HURRICANE |
| | ANCHOR SCHEDULE. ROOF FRAMING PLAN AND |
| | WALL SECTIONS SPECIFY DIFFERENT |
| | CONNECTORS. |
| | -INCLUDE CONNECTORS TO BE USED AT |
| | EXISTING BEARING WALL AND NEW TRUSSES. |
| | 7-CLEARLY SPECIFY THE DESIGN PRESSURES |
| | CALCULATED FOR ALL EXTERIOR OPENINGS. |
| | SEC. 1606 SBC 1997. |
| | 8-CLEARLY SPECIFY SIZES AND SPACING OF |
| | ATTIC VENTS AT FLAT ROOF AREA. ALSO, |
| | SPECIFY ATTIC VENTILATION AT TYP. WALL |
| | SECTION. SEC. 2309.7 SBC 1997. |
| | 9-CLARIFY HOWIS THE TYP. EXTERIOR WALL |
| | SECTION GOING TO ACHIEVE INSULATION |
| | WITH AN R-11 VALUE. |
| | 10-DETAILS SHEET: CLEARLY INDICATE THE |
| | DETAILS THAT APPLY TO THIS PROJECT. |
| | -INDICATE ON PLANS WHERE ARE THE WALL |
| | SECTIONS TAKEN AT. |
| | 11-ROOF FRAMING PLAN IS INCOMPLETE. IT |
| | DOESN'T MATCH WHAT IS SHOWN ON EXTER'R |
| | ELEVATIONS. |
| | 12-ROOF PITCH OF 2:12 NEEDS TWO LAYERS |
| | OF UNDERLAYMENT. SEC. 1504.2.1 SBC/97. |
| | 13-PROVIDE COMPLETE INFORMATION FOR |
| | INSTALLATION OF ACCORDION STORM |
| | SHUTTERS. PROVIDE KEY PLAN AND CLEARLY |
| | INDICATE ON DRAWINGS THE COMPONENTS |
| | AND ANCHORS SELECTED FOR THIS SPECIFIC |
| | INSTALLATION. |
| | 14-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | PLEASE RETURN REVIEWED SET IN ORDER TO |
| | EXPEDITE THE REVIEW PROCESS. |
| | 15-PROVIDE SOIL TEST REPORT. SECTION |
| | 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| | 16-ENGINEER TO PROVIDE ALL INFORMATION, |
| | INCLUDING HIS LICENSE NUMBER IN ALL |
| | DRAWINGS AS REQUIRED BY CHAPTER 471 OF |
| | FLORIDA STATUTES. |