Plan Review Notes
Plan Review Notes For Permit 01110090
Permit Number 01110090
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2002-06-05 00:00:001) THE PARKING GARAGE IS REQUIRED TO
 BE CONTINOUSLY VENTILATED PER THE
 APPLICABLE CODE REQUIREMENTS FOR
 ENCLOSED PARKING GARAGES. SINCE NO
 EMERGENCY POWER IS PLANNED, PLEASE
 PROVIDE THIS OFFICE IN WRITING THAT
 SHOULD ELECTRICAL POWER BE LOST, THAT
 THE ENCLOSED PARKING GARAGE WILL BE
 CLOSED UNTIL SUCH TIME THAT NORMAL
 POWER IS RESTORED.
  
 2) ELEVATIONS ON BOTH SIDES OF EXIT
 DOORS ARE TO BE EQUAL FOR THE WIDTH
 OF THESE DOORS WHEN OPENED.
  
 3) WHEN THE 60" SECURITY GATES ARE
 CLOSED HOW DOES THIS COMPROMISE
 EXITING FROM THE GARAGE. PLEASE
 EXPLAIN.
  
 4) SINCE THE PARKING GARAGE IS
 CONSIDERED A CLOSED AND NO FIRE
 SPRINKLER PROTECTION IS PLANNED, A
 FIRE ALARM SYSTEM WILL BE REQUIRED AS
 PER NFPA 88A. PLEASE ADVISE THIS OFFICE
 HOW THIS WILL BE ACCOMPLISHED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910