| Notes |
| Date |
Text |
| 2002-06-05 00:00:00 | 1) THE PARKING GARAGE IS REQUIRED TO | | | BE CONTINOUSLY VENTILATED PER THE | | | APPLICABLE CODE REQUIREMENTS FOR | | | ENCLOSED PARKING GARAGES. SINCE NO | | | EMERGENCY POWER IS PLANNED, PLEASE | | | PROVIDE THIS OFFICE IN WRITING THAT | | | SHOULD ELECTRICAL POWER BE LOST, THAT | | | THE ENCLOSED PARKING GARAGE WILL BE | | | CLOSED UNTIL SUCH TIME THAT NORMAL | | | POWER IS RESTORED. | | | | | | 2) ELEVATIONS ON BOTH SIDES OF EXIT | | | DOORS ARE TO BE EQUAL FOR THE WIDTH | | | OF THESE DOORS WHEN OPENED. | | | | | | 3) WHEN THE 60" SECURITY GATES ARE | | | CLOSED HOW DOES THIS COMPROMISE | | | EXITING FROM THE GARAGE. PLEASE | | | EXPLAIN. | | | | | | 4) SINCE THE PARKING GARAGE IS | | | CONSIDERED A CLOSED AND NO FIRE | | | SPRINKLER PROTECTION IS PLANNED, A | | | FIRE ALARM SYSTEM WILL BE REQUIRED AS | | | PER NFPA 88A. PLEASE ADVISE THIS OFFICE | | | HOW THIS WILL BE ACCOMPLISHED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|