 PLAN SHEET M2 INDICATE REFRIGERATION
 LINES RUNNING THROUGH THE STAIRWELL.
 AS PER 1997 SBC 1006.1.3.1,
 PENETRATIONS INTO AND OPENINGS THROUGH
 A STAIRWAY ENCLOSURE ASSEMBLY ARE
 PROHIBITED.
  
 PROVIDE INFORMATION FOR THE EXHAUST DUCT
 FOR THE GARAGE.SHOW COMPLIANCE WITH
 1997 SMC 610.4, IN BUILDINGS MORE THAN
 ONE STORY IN HEIGHT, DUCTS EXTENDING
 THROUGH MORE THAN ON FLOOR SHALL BE
 PROTECTED BY A SHAFT ENCLOSURE WITH A
 FIRE RESISTANCE RATING OF NOT LESS THAN
 1 HOUR.