| Notes |
| Date |
Text |
| 2002-03-18 00:00:00 | | | | PLAN SHEET M2 INDICATE REFRIGERATION | | | LINES RUNNING THROUGH THE STAIRWELL. | | | AS PER 1997 SBC 1006.1.3.1, | | | PENETRATIONS INTO AND OPENINGS THROUGH | | | A STAIRWAY ENCLOSURE ASSEMBLY ARE | | | PROHIBITED. | | | | | | PROVIDE INFORMATION FOR THE EXHAUST DUCT | | | FOR THE GARAGE.SHOW COMPLIANCE WITH | | | 1997 SMC 610.4, IN BUILDINGS MORE THAN | | | ONE STORY IN HEIGHT, DUCTS EXTENDING | | | THROUGH MORE THAN ON FLOOR SHALL BE | | | PROTECTED BY A SHAFT ENCLOSURE WITH A | | | FIRE RESISTANCE RATING OF NOT LESS THAN | | | 1 HOUR. |
|