| Plan Review Notes For Permit 01110090 |
| Permit Number |
01110090 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-03-14 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE WRONG CODE(S) ARE | | | STILL REFERENCED. NOTE MENTIONS, SBCCI | | | FOR ELEC? AND "96" NEC? WE ARE UNDER THE | | | "99" NEC AND ALSO CODES REF IN LOWER | | | NOTES, GIVE CODES FROM '96'. | | | PLEASE CORRECT. | | | | | | 2)NOTE: PLEASE GO OVER LOADS ADDED FOR | | | PANEL "B". | | | PLEASE NOTE THAT ALL CONTINUOUS LOADS | | | NEED TO BE SHOWN AT 125%.230-42/215-2,3 | | | AND 220-13 FOR RECEPT LOADS NOT SHOWN. | | | | | | 3)NOTE: PLEASE NOTE THAT PANEL "A/C" | | | IS SHOWN ON PANEL SCHEDULE AS 3-PHASE, | | | 4 WIRE. PLEASE NOTE ONLY 3 CONDUCTORS | | | ARE SHOWN ON RISER DIAGRAM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|