Plan Review Notes
Plan Review Notes For Permit 01110090
Permit Number 01110090
Review Stop P
Sequence Number 1
Notes
Date Text
2001-11-28 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT CV, GEN NOTES #3, 1999 SO. FLA.
 BLDG CODE BROWARD CO. EDITION SHOULD
 READ STANDARD BLDG CODE 1997.
 2) SHT A3 LUNCH ROOM 214, SINK TO COMPLY
 WITH FACBC 2.24. PLEASE SHOW DETAILS.
 3) STH P4 PER MODEL COUNTYWIDE AMEND-
 MENTS TO SPC-94 SEC 607.7 ONLY 2 FIX-
 TURES ON 1/2" COLD WATER LINE AND ONLY
 4 FIXTURES ON 1/2" HOT. PLEASE CHANGE
 COLD WATER LINE TO TOILET ROOMS TO RE-
 FLECT WATER RISER DIAGRAM.
 4) SHT P4 PER MODEL COUNTYWIDE AMEND-
 MENTS TO SPC SEC 507.8.1, 1" DRAIN REQ-
 UIRED FOR PAN DRAIN FOR WATER HEATER.
 5) ALL WATER HEATERS ON SHELVES TO HAVE
 PERMINATE SHIPS LADDER AND MINIMUM WORK-
 ING PLATFORM 30"X30". EITHER PROVIDE A
 DETAIL FOR THESE OR PUT HEATER ON FLOOR.
 6) SHT P5 WATER HEATER DETAIL, P/T AND
 PAN DRAIN TO RUN SEPARATELY. SPC SEC
 507.8.4.
 7) SHT P5 PLUMB. NOTES #5 SANITARY DRAIN
 AGE MATERIAL SHALL BE EITHER PVC OR CAST
 IRON, NOT ONE MATERIAL IN WALLS AND THE
 OTHER OUTSIDE WALLS.
 8) SHT P6 SANT RISER DIAGRAM, 2-WAY C/O
 REQUIRED NEAR JUNCTION OF BLDG DRAIN AND
 BLDG SEWER.
 9) SHT P6, PLEASE INDICATE WATER HAMMER
 ARRESTORS ON WATER RISER DIAGRAM. AIR
 CHAMBERS REQUIRE ACCESS PANELS AND SHALL
 BE RECHARGEABLE IF USED. PLEASE INDICATE
 BRAND AND MODEL # OF WATER HAMMER ARRES-
 TORS.
 10) SHTS A6 & P7, PLEASE PROVIDE ROOF
 DRAINAGE CALCULATIONS FOR PRIMARY AND
 SECONDARY DRAINS. SIZE PER SPC SEC 1108
 & 1109. INCLUDE 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPET WALLS 1108.3.
 ALSO INCLUDE AREA OF ROOF THAT DRAINS ON
 TO ROOF. PLEASE PROVIDE STORM RISER DIA-
 GRAM. INCLUDE PIPE SIZE AND SQ FT AREA
 DRAINED FOR EACH SECTION OF PIPE AND FOR
 EACH DRAIN.
  