| 2001-11-28 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) SHT CV, GEN NOTES #3, 1999 SO. FLA. |
| | BLDG CODE BROWARD CO. EDITION SHOULD |
| | READ STANDARD BLDG CODE 1997. |
| | 2) SHT A3 LUNCH ROOM 214, SINK TO COMPLY |
| | WITH FACBC 2.24. PLEASE SHOW DETAILS. |
| | 3) STH P4 PER MODEL COUNTYWIDE AMEND- |
| | MENTS TO SPC-94 SEC 607.7 ONLY 2 FIX- |
| | TURES ON 1/2" COLD WATER LINE AND ONLY |
| | 4 FIXTURES ON 1/2" HOT. PLEASE CHANGE |
| | COLD WATER LINE TO TOILET ROOMS TO RE- |
| | FLECT WATER RISER DIAGRAM. |
| | 4) SHT P4 PER MODEL COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC 507.8.1, 1" DRAIN REQ- |
| | UIRED FOR PAN DRAIN FOR WATER HEATER. |
| | 5) ALL WATER HEATERS ON SHELVES TO HAVE |
| | PERMINATE SHIPS LADDER AND MINIMUM WORK- |
| | ING PLATFORM 30"X30". EITHER PROVIDE A |
| | DETAIL FOR THESE OR PUT HEATER ON FLOOR. |
| | 6) SHT P5 WATER HEATER DETAIL, P/T AND |
| | PAN DRAIN TO RUN SEPARATELY. SPC SEC |
| | 507.8.4. |
| | 7) SHT P5 PLUMB. NOTES #5 SANITARY DRAIN |
| | AGE MATERIAL SHALL BE EITHER PVC OR CAST |
| | IRON, NOT ONE MATERIAL IN WALLS AND THE |
| | OTHER OUTSIDE WALLS. |
| | 8) SHT P6 SANT RISER DIAGRAM, 2-WAY C/O |
| | REQUIRED NEAR JUNCTION OF BLDG DRAIN AND |
| | BLDG SEWER. |
| | 9) SHT P6, PLEASE INDICATE WATER HAMMER |
| | ARRESTORS ON WATER RISER DIAGRAM. AIR |
| | CHAMBERS REQUIRE ACCESS PANELS AND SHALL |
| | BE RECHARGEABLE IF USED. PLEASE INDICATE |
| | BRAND AND MODEL # OF WATER HAMMER ARRES- |
| | TORS. |
| | 10) SHTS A6 & P7, PLEASE PROVIDE ROOF |
| | DRAINAGE CALCULATIONS FOR PRIMARY AND |
| | SECONDARY DRAINS. SIZE PER SPC SEC 1108 |
| | & 1109. INCLUDE 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPET WALLS 1108.3. |
| | ALSO INCLUDE AREA OF ROOF THAT DRAINS ON |
| | TO ROOF. PLEASE PROVIDE STORM RISER DIA- |
| | GRAM. INCLUDE PIPE SIZE AND SQ FT AREA |
| | DRAINED FOR EACH SECTION OF PIPE AND FOR |
| | EACH DRAIN. |
| | |
| | REVIEW BY KEN STEVENS |