2001-12-11 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PLEASE INDICATE IF GARAGE IS OPEN
 OR CLOSED AS DEFINED IN THE 1997 SBC
 411.3.2 THRU 411.3.4.
  
 2.ENCLOSED PARKING GARAGES SHALL
 COMPLY WITH 1997 SBC 411.4.2, FOR
 VENTILATION REQUIREMENTS.PLEASE
 INDICATE ON PLANS ALL EQUIPMENT AND
 VENTILATION CALCULATIONS FOR THE
 GARAGE AREA.
  
 3.CONDENSERS ARE TO BE LOCATED IN THE
 GARAGE AREA.PROVIDE INFORMATION
 ON HOW THE EQUIPMENT IS BEING
 PROTECTED FROM DAMAGE.CONDENSER
 LOCATED OUTSIDE OF ELEV RM 106,
 SEEMS TO BE OBSTRUCTING THE ENTRANCE
 TO THE ELEV RM.
  
 4.PLAN SHEET DUCT PENETRATING THE
 FLOOR, TO LOBBY AREA (101) DOES NOT
 INDICATE A FIRE DAMPER.
  
 5.PLAN SHEET M2, RETURN AIR DUCT FOR
 AHU-4 IS RUNNING THROUGH THE STAIR-
 WELL # 2.AS PER 1997 SBC
 1006.1.3.1,PENETRATIONS INTO AND
 OPENINGS THROUGH A STAIRWAY
 ENCLOSURE ASSEMBLY ARE PROHIBITED
 EXCEPT FOR REQUIRED EXIT DOORS, DUCT
 WORK & EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, AND
 ELECTRICAL CONDUIT SERVING THE
 STAIRWAY AND TERMINATING AT A STEEL
 BOX NOT EXCEEDING 16 SQ IN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.