| 2001-12-11 00:00:00 | ********************DENIED************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | 1.PLEASE INDICATE IF GARAGE IS OPEN |
| | OR CLOSED AS DEFINED IN THE 1997 SBC |
| | 411.3.2 THRU 411.3.4. |
| | |
| | 2.ENCLOSED PARKING GARAGES SHALL |
| | COMPLY WITH 1997 SBC 411.4.2, FOR |
| | VENTILATION REQUIREMENTS.PLEASE |
| | INDICATE ON PLANS ALL EQUIPMENT AND |
| | VENTILATION CALCULATIONS FOR THE |
| | GARAGE AREA. |
| | |
| | 3.CONDENSERS ARE TO BE LOCATED IN THE |
| | GARAGE AREA.PROVIDE INFORMATION |
| | ON HOW THE EQUIPMENT IS BEING |
| | PROTECTED FROM DAMAGE.CONDENSER |
| | LOCATED OUTSIDE OF ELEV RM 106, |
| | SEEMS TO BE OBSTRUCTING THE ENTRANCE |
| | TO THE ELEV RM. |
| | |
| | 4.PLAN SHEET DUCT PENETRATING THE |
| | FLOOR, TO LOBBY AREA (101) DOES NOT |
| | INDICATE A FIRE DAMPER. |
| | |
| | 5.PLAN SHEET M2, RETURN AIR DUCT FOR |
| | AHU-4 IS RUNNING THROUGH THE STAIR- |
| | WELL # 2.AS PER 1997 SBC |
| | 1006.1.3.1,PENETRATIONS INTO AND |
| | OPENINGS THROUGH A STAIRWAY |
| | ENCLOSURE ASSEMBLY ARE PROHIBITED |
| | EXCEPT FOR REQUIRED EXIT DOORS, DUCT |
| | WORK & EQUIPMENT NECESSARY FOR |
| | INDEPENDENT STAIR PRESSURIZATION, |
| | SPRINKLER PIPING, STANDPIPES, AND |
| | ELECTRICAL CONDUIT SERVING THE |
| | STAIRWAY AND TERMINATING AT A STEEL |
| | BOX NOT EXCEEDING 16 SQ IN. |
| | |