Plan Review Notes
Plan Review Notes For Permit 01110090
Permit Number 01110090
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-12-10 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) WHAT PROVISIONS HAVE BEEN MADE FOR
 FIRE RESCUE ACCESS WHEN THE SECURITY
 GATES ARE CLOSED. SECURITY GATES REQUIRE
 SEPARATE PLANS AND PERMITS.
 3) A TWO HOUR FIRE SEPARATION IS
 REQUIRED FROM THE PARKING AREA TO ANY
 OTHER PARTS OF THE STRUCTURE.
 4) PLEASE INDICATE PERCENTAGE OF WALL
 OPENINGS FOR THE PARKING AREA. PLANS
 INDICATE ECONO-RAIL MESH PANELS. PLEASE
 INDICATE ON PLANS IF THE PARKING AREA
 IS CONSIDERED OPEN OR CLOSED.
 5) ELEVATOR TO COMPLY WITH ANSI A17.1.
 6) RECEPTION AREA NOTED ON SECOND FLOOR
 FURNITURE PLAN DOES NOT APPEAR TO ALLOW
 FOR THE REQUIRED 44" AISLE.
 7) HOW IS EXITING ACCOMPLISHED FROM THE
 PARKING AREA WHEN THE SECURITY GATES
 ARE CLOSED OR IN THE DOWN POSITION.
 8) PLEASE INDICATE ALL FIRE RATINGS
 FOR THE BUILDING. SINCE NO FIRE
 SPRINKLERS ARE PRESENT, ALL EXIT ACCESS
 AREAS ARE TO BE SEPARATED FROM OTHER
 AREAS BY AT LEAST ONE HOUR.
 9) PLEASE EXPLAIN SECURITY FEATURES PLAN
 NED FOR ANY AND ALL EXIT DOORS.
 10) PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS OF THE BUILDING.
 11) PLEASE PROVIDE FIRE ALARM EQUIPMENT
 LOCATIONS.
 12) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910