| 2001-12-10 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE 3343-00. |
| | 2) WHAT PROVISIONS HAVE BEEN MADE FOR |
| | FIRE RESCUE ACCESS WHEN THE SECURITY |
| | GATES ARE CLOSED. SECURITY GATES REQUIRE |
| | SEPARATE PLANS AND PERMITS. |
| | 3) A TWO HOUR FIRE SEPARATION IS |
| | REQUIRED FROM THE PARKING AREA TO ANY |
| | OTHER PARTS OF THE STRUCTURE. |
| | 4) PLEASE INDICATE PERCENTAGE OF WALL |
| | OPENINGS FOR THE PARKING AREA. PLANS |
| | INDICATE ECONO-RAIL MESH PANELS. PLEASE |
| | INDICATE ON PLANS IF THE PARKING AREA |
| | IS CONSIDERED OPEN OR CLOSED. |
| | 5) ELEVATOR TO COMPLY WITH ANSI A17.1. |
| | 6) RECEPTION AREA NOTED ON SECOND FLOOR |
| | FURNITURE PLAN DOES NOT APPEAR TO ALLOW |
| | FOR THE REQUIRED 44" AISLE. |
| | 7) HOW IS EXITING ACCOMPLISHED FROM THE |
| | PARKING AREA WHEN THE SECURITY GATES |
| | ARE CLOSED OR IN THE DOWN POSITION. |
| | 8) PLEASE INDICATE ALL FIRE RATINGS |
| | FOR THE BUILDING. SINCE NO FIRE |
| | SPRINKLERS ARE PRESENT, ALL EXIT ACCESS |
| | AREAS ARE TO BE SEPARATED FROM OTHER |
| | AREAS BY AT LEAST ONE HOUR. |
| | 9) PLEASE EXPLAIN SECURITY FEATURES PLAN |
| | NED FOR ANY AND ALL EXIT DOORS. |
| | 10) PLEASE INDICATE INTERIOR FINISH FOR |
| | WALLS AND CEILINGS OF THE BUILDING. |
| | 11) PLEASE PROVIDE FIRE ALARM EQUIPMENT |
| | LOCATIONS. |
| | 12) PLEASE INDICATE FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |