Plan Review Notes
Plan Review Notes For Permit 01110090
Permit Number 01110090
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-11-21 00:00:00FAILED :
 1. PLEASE PROVIDE STORM WATER CALC.
 FOR OUR REVIEW AND APPROVAL.
 2. PLEASE PROVIDE PERVIOUS AND
 IMPERVIOUS CALC. FOR ENTIRE SITE.
 3. PLEASE STATE IF THE EXISTING METER,
 WATER SERVICE AND SEWER LATERAL, BACK-
 FLOW PREVENTERS ARE ADEQUATE, ALL NEW
 CONNECTIONS HAVE TO BE APPROVED BY
 UTILITIES DEPARTMENT, 659-8040.
 4. PLEASE PROVIDE POLLUTION PREVENTION
 PLANS FOR ENTIRE SITE, PLANS MUST BE
 INSTALLED IN FIELED PRIOR ANY EARTH WORK
 5. ALL OFF-STREET PARKING MUST BE
 STRIPED WITH DOUBLE 4" WHITE AND BLUE
 (H.C).
 6. IS THE TYPE C CATCH BASIN LOCATED AT
 THE SOUTH ENTRACENCE A CONTROL STRUCTURE
 ALSO THE EXSITING STRUCTURE MUST BE
 THAT BEING CONNECTED TO MUST BE SHOWN.
 7. CITY'S STANDARD MAY BE OBTAINED FROM
 PUBLIC UTILITIES DEPT. 659-8040.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8482 MOHAMMAD R. AMINI