| Plan Review Notes For Permit 01110090 |
| Permit Number |
01110090 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-26 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOTE "NOTE 1" | | | ON ELECTRICAL NOTES NEEDS TO REFERENCE | | | LOCAL AMENDMENTS ALSO. | | | | | | 2)NOTE: PLEASE CLARIFY METHOD OF THE | | | EQUIPMENT GROUNDING BETWEEN MAIN DISC`S | | | AND PANELS. 250-122 | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4)NOTE: PLEASE NOTE THE CODES REFERENCED | | | CODES, ARE FROM THE "96" NEC. | | | | | | 5)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 215-5,220-10,220-11,220-3,AND 220-13 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|