2001-11-26 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOTE "NOTE 1"
 ON ELECTRICAL NOTES NEEDS TO REFERENCE
 LOCAL AMENDMENTS ALSO.
  
 2)NOTE: PLEASE CLARIFY METHOD OF THE
 EQUIPMENT GROUNDING BETWEEN MAIN DISC`S
 AND PANELS. 250-122
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE NOTE THE CODES REFERENCED
 CODES, ARE FROM THE "96" NEC.
  
 5)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 215-5,220-10,220-11,220-3,AND 220-13
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  