Plan Review Notes
Plan Review Notes For Permit 01110090
Permit Number 01110090
Review Stop B
Sequence Number 1
Notes
Date Text
2001-12-14 00:00:00THIS BUILDING WILL BE A TWO STORY
 STRUCTURE INSIDE THE DESIGNATED FIRE
 DISTRICT AND IS REQUIRED BY SBC
 F102.2.5 TO BE 1 HOUR PROTECTED.
 (APPENDIX F)
  
 THE PARKING AREA IS A PARKING GARAGE
 AND BEING PROPOSED TO BE ZERO LOT LINE,
 IS REQUIRED BY SBC TABLE 600 TO HAVE 1
 HOUR FIRE RATED WALLS WITH NO OPENINGS.
  
  
 GIVEN THE ABOVE REQUIREMENTS, THE GARAGE
 MUST COMPLY WITH SBC 411.4, MECHANICAL
 VENTILATION SYSTEMS.
  
 AT TIME OF PERMIT APPLICATION INCLUDE A
 LIFE SAFETY PLAN FOR THE EXISTING
 BUILDING SHOWING THE EXIT DISCHARGE,
 SBC 1010, FOR THE REAR EXITS, (EAST
 SIDE).SEE ALSO SBC 1001.1.3 AS IT
 APPEARS THAT THEY WILL DISCHARGE INTO
 THE GARAGE.
  
 AT TIME OF PERMIT APPLICATION SHOW HOW
 THE EXTERIOR GLAZED PORTIONS OF THE
 BUILDING WILL COMPLY WITH THE CITY'S
 HURRICANE MISSILE IMPACT REQUIREMENTS.
 SEE ATTACHED INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY FOR THE CITY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 AT TIME OF PERMIT APPLICATION TEST
 REPORTS OR NOTICE OF ACCEPTANCE REPORTS
 MUST BE PROVIDED FOR THE WINDOWS, DOORS
 AND ROOF COVERINGS.
  
 SHEET A6.02 SHOWS THE EMERGENCY OVERFLOW
 SCUPPER LEVEL WITH THE ROOF.SEE SBC
 1517.6.4.
  
 SHEET A7 SHOWS PLYWOOD ROOF SHEATHING
 PROPOSED.THE USE OF COMBUSTIBLE
 COMPONENTS WILL MAKE THIS A TYPE V
 BUILDING NOT A TYPE IV. SBC TABLE 600
 REQUIRES A HIGHER HOURLY FIRE RATING
 FOREXTERIOR WALLS OF TYPE V
 CONSTRUCTIONTHAN TYPE IV. REVISE
 ACCORDINGLY PRIOR
 TO PERMIT APPLICATION.
  
 THE REQUIREMENTS OF SBC 1803.2 MUST BE
 COMPLIED WITH REGARDING FOUNDATION
 CONSTRUCTION.
  
 THE FIRE DOOR RATING FOR THE STAIR
 ENCLOSURES MUST COMPLY WITH SBC
 705.1.3.4.
  
 SHOW THE DETAILS FOR THE EXTERIOR BRICK
 VENEER IN ACCORDANCE WITH SBC 1403.2.
  
 SHEET S-8 CITES ASCE 7-93 AS THE DESIGN
 STANDARD.SBC 1997 INVOKES ASCE 7-95.
 PLEASE REVISE AS NECESSARY AND
 DEMOMNSTRATE COMPLIANCE WITH SAME. SEE
 SBC 1606.1.
  
 THE PLANS DO NOT CLEARLY INDICATE THE
 DESIGN AND LOADINGS FOR THE VARIOUS
 HAND AND GUARD RAILS.SEE SBC 1007.5,
 1015 AND 1608.2.
  
 THE STRUCTURAL PLANS DO NOT DECLARE THE
 PILING DESIGN LOADS. SEE SBC 1806.
  
 NOTE, THIS IS A PAID PLAN REVIEW AND NOT
 A PERMIT APPLICATION.AT THE PRESENT
 TIME IT IS LIKELY THAT THE NEW FORIDA
 BUILDING CODE WILL TAKE EFFECT MARCH 1,
 2002.