Text |
| 2001-11-28 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) SHT A2.1 PLEASE SUBMIT CALCULATIONS |
| | FOR MINIMUM FIXTURES PER SPC TABLE 407. |
| | 2) SHT A2.3 PLEASE SUBMIT CALCULATIONS |
| | FOR ROOF DRAINAGE, PRIMARY AND SECONDARY |
| | DRAINS USING SPC SEC 1108 & 1109. ADD |
| | 1/2 THE AREA OF ALL VERTICAL WALLS AND |
| | INCLUDE AREA OF UPPER ROOFS DRAINING ON |
| | TO ROOF. SHOW LOCATION OF SCUPPERS THAT |
| | DRAIN TYPICAL ROOFS AT CORNERS. |
| | 3) PLEASE PROVIDE A STORM RISER DIAGRAM |
| | WITH ALL SQ FOOTAGE SHOWN AT EACH SECT- |
| | ION. |
| | 4) SHT A7.1 DETAIL #4 PLEASE SHOW DETAIL |
| | OF FACBC SEC 4.18.2 & 4.18.3 FOR URNAL. |
| | 5) SHT A7.1 DETAIL #11 PLEASE SHOW DE- |
| | TAIL FOR KITCHEN SINK SEC 4.24.2, 4.24.3 |
| | AND 4.24.4 FACBC. |
| | 5) SHT P0.1 PLUMBING NOTES #13, AIR |
| | CHAMBERS TO BE ACCESSIBLE AND RECHARGE- |
| | ABLE IF USED. WATER HAMMER ARRESTORS DO |
| | NOT NEED ACCESS IF APPROVED TYPE. |
| | 6) SHT PO.2 PLEASE PROVIDE A WATER RISER |
| | DIAGRAM WITH PIPE SIZES AND SHOW WATER |
| | HAMMER ARRESTORS LOCATED CLOSE TO FIX- |
| | TURES IN AN "EFFECTIVE RANGE" NOT AT TOP |
| | OF DROP. |
| | 7) IRRIGATION, LICENSED PLUMBING CONTRAC |
| | TOR TO SUPPLY A VALVE, WATTS-N36 VACUUMN |
| | BREAKER ABOVE GROUND FOR IRRIGATION FROM |
| | POTABLE WATER. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |