| Plan Review Notes For Permit 01110060 |
| Permit Number |
01110060 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-12-08 00:00:00 | ******************DENIED**************** | | | | | | | | | AS PER FIRE DEPT COMMENTS ALL STORAGE & | | | ELECTICAL ROOMS ARE TO BE FIRE RATED. | | | PLEASE IDENTIFY FIRE DAMPERS ON PLAN. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS. (NFPA 90A | | | 4-4.4.3) | | | | | | ADDITIONAL PERMIT REQUIRED FOR HOOD AND | | | FIRE SUPRESSION.PLEASE PROVIDE PLANS | | | AND MANUFACTURER SUBMITTAL DATA/PRODUCT | | | APPROVALS WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|