| Plan Review Notes For Permit 01110060 |
| Permit Number |
01110060 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-26 00:00:00 | 1) IT DEPENDS WHEN THE BUILDING IS | | | OFFICIALLY PERMITTED WHAT FIRE CODE | | | WILL BE USED. ON JANUARY 1, 2002, THE | | | FLORIDA FIRE PREVENTION CODE WILL BE | | | USED WHICH INVOKES THE 2000 EDITION | | | OF THE LIFE SAFETY CODE. | | | 2) SINCE NO FIRE SPRINKLER SYSTEM IS | | | PLANNED, ALL STORAGE ROOMS, AND | | | ELECTRICAL ROOM ARE TO BE FIRE RATED. | | | 3) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD,DUCT,AND EXTINGUISHING SYSTEM | | | PLANNED FOR KITCHEN. | | | 5) BOARDROOM DOORS MUST SWING IN THE | | | DIRECTION OF EXIT TRAVEL. PRELIMINARY | | | OCCUPANT LOAD CALCULATIONS INDICATE | | | LOADS OF 50 OR MORE PERSONS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT. 8497 | | | 835-2910 |
|