| Plan Review Notes For Permit 01110060 |
| Permit Number |
01110060 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-26 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | NEED TO BE SHOWN. PLANS HAVE BEEN DONE\\ | | | WITH CONNECTED LOADS SHOWN IN THE PAST, | | | LOAD CALCS ARE REQ`D TO BE SHOWN. | | | PER 215-5, 220-3,220-10,220-11,220-13 | | | PLEASE NOTE THAT ALL CONTINUOUS LOADS | | | NEED TO BE SHOWN AT 125% PER 230-42,215- | | | 3. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|