| 2001-12-18 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE |
| | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | 1) SBC* 104.2.3NONE OF THE THREE SETS |
| | OF PLANS SUBMITTED HAVE ALL OF THE |
| | ARCHITECTURAL PLANS PROPERLY SEALED.AT |
| | LEAST ONE SET OF PLANS SHALL BE SIGNED |
| | AND SEALED. |
| | |
| | 2) SBC 1012.1.2THE BOARD ROOM CAN |
| | ACCOMMODATE MORE THAN 50 OCCUPANTS.THE |
| | DOORS SHALL OPEN IN THE DIRECTION OF |
| | EGRESS. |
| | |
| | 3) SBC 704.1.3.3.1IF THE WATER HEATER/ |
| | BOILER EXCEEDS A HEAT INPUT CAPACITY OF |
| | 200 000 BTUH OR A WATER TEMPERATURE OF |
| | 210 DEGREES-F OR A NOMINAL WATER |
| | CAPACITY OF 120 GALLONS, IT SHALL BE |
| | SEPARATED FROM THE REST OF THE BUILDING |
| | BY 1-HOUR FIRE-RESISTANT CONSTRUCTION. |
| | CONFIRM WHETHER THIS IS APPLICABLE. |
| | |
| | 4) SBC* 1503.1.3.2THE ABOVE-DECK ROOF |
| | INSULATION SHALL BE MECHANICALLY |
| | FASTENED. |
| | |
| | 5) SBC 1503.1.5THE KITCHEN AIR INTAKE |
| | DUCT SHALL BE INSTALLED TO LEAVE AT |
| | LEAST 18" CLEARANCE FOR ACCESS TO THE |
| | ROOF COVERING. |
| | |
| | 6) SBC 1403.2.1THE DECORATIVE CAST |
| | STONE PANELS (SHEET A5.2, DETAIL 1) |
| | SHALL BE NOT LESS THAN 1 5/8" THICK AND |
| | FIXED IN ACCORDANCE WITH SBC 1403.2.8. |
| | |
| | 7) SBC* 1804.2.2SHEET S-3. FOUNDATION |
| | NOTE 1A REFERS TO A SOIL REPORT BY |
| | ARDAMAN AND ASSOCIATES.A SOIL REPORT |
| | SHALL BE SUBMITTED. |
| | |
| | 8) FL ACC CODE 4.6.3THE TWO ACCESSIBLE |
| | PARKING SPACES SHALL EACH BE AT LEAST |
| | 12' WIDE AND THE COMMON ACCESS AISLE AT |
| | LEAST 5' WIDE.WHILST SHEET A1.2 SHOWS |
| | ADEQUATE WIDTH, SHEET A1.1 SHOWS AN |
| | OVERALL WIDTH LESS THAN THE REQUIRED |
| | MINIMUM. |
| | |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |