| Date |
Text |
| 2001-11-30 00:00:00 | APPROVED WITH PROVISO: |
| | 1-REVISE THE ENERGY CALCULATIONS: |
| | -UNDER ATTIC AREA IS INCORRECT. SEE |
| | SECTION 604.1.A.1 OF FLORIDA ENERGY |
| | CODE FOR BUILDING CONSTRUCTION, 1997. |
| | 2-PROVIDE CURRENT UL ASSEMBLY # FOR ONE |
| | HR FIRE RATED GLASS BLOCK ASSEMBLY. |
| | 3-PROVIDE UPDATED PRODUCT APPROVAL FOR |
| | ENTRY DOORS. |
| | 4-PROVIDE STRUCTURAL HANGING DETAIL FOR |
| | AHU. SPECIFY ALL CONNECTORS. SECTION |
| | 104.2.2 OF CITY AMENDMENTS TO SBC 1997 |
| | 5-REVISE WINDOW SIZE FOR BEDROOM #3. |
| | 24SH WINDOW DOESN'T MEET THE MINIMUM |
| | CLEAR HEIGHT OPENING OF 24". |
| | SECTION 1005.4 SBC 1997. |
| | 6-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS AND SEC. 2405.2 SBC 1997. |
| | 7-TRUSS DRAWINGS: |
| | -UPDATE GENERAL TRUSS DETAILS. USE ASCE |
| | 7-95 FOR 140MPH, NOT ASCE 7-93 FOR 110 |
| | -REVIEW STAMP BY ENGINEER OF RECORD |
| | DOESN'T IDENTIFY FIRM WHO REVIEWED IT. |
| | 8-SOIL TEST REPORT ENGINEER TO PROVIDE |
| | ORIGINAL SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 OF FLORIDA STATUTES. |
| | 9-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | PLEASE BRING BACK REVIEWED SETS AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| | IN ORDER TO EXPEDITE THE REVIEW. |