| 2001-12-01 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMENCEMENT. |
| | 2-PROVIDE COMPLETE SECTION/DETAIL AT |
| | INTERIOR BEARING WALL BETWEEN GARAGE |
| | AND FOYER SHOWING RECESS AT GARAGE. |
| | SEE SIZE OF FOOTING SPECIFIED. |
| | SPECIFY ALL FASTENERS. |
| | 3-REVISE ATTIC ACCESS SIZE AT MASTER |
| | BEDRM. SEE PLANS & SEC. 2309.6 SBC/97. |
| | ALSO, REVISE DETAIL D/2. |
| | 4-SPECIFY CONNECTORS AT BOTTOM OF STEEL |
| | COLUMNS AT REAR PORCH. SEC. 104.2.2 |
| | CITY AMENDMENTS TO SBC 1997. |
| | 5-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS. SEC. 2405.2 SBC 1997. |
| | 6-CLEARLY INDICATE ON PLANS THE OPTIONS |
| | THAT ARE GOING TO BE BUILT. CROSS OUT |
| | THE OTHERS. |
| | 7-PROVIDE PRODUCT APPROVAL FOR: |
| | A)FRENCH DOORS WITH SIDELITES SINGLE |
| | ASSEMBLY IF OPTION IS SELECTED. |
| | B)FIXED GLASS AT BREAKFAST AREA. SEE |
| | SIZE SHOWN ON PLANS. |
| | C)ENTRY DOORS PRODUCT APPROVAL EXPIRED. |
| | 8-REVISE ENERGY CALCULATIONS: |
| | -UNDER ATTIC AREA IS INCORRECT. SEE |
| | SEC. 604.1.A.1 OF FL. ENERGY CODE,1997 |
| | 9-CONNECTOR SPECIFIED FOR TRUSS H7B DOES |
| | NOT RESIST THE UPLIFT LOADS. SEE |
| | ENGINEERED TRUSSES. |
| | 10-ROOF TRUSSES: |
| | -UPDATE ALL GENERAL DETAILS. USE ASCE |
| | 7-95 FOR 140MPH, NOT ASCE 7-93. SEE |
| | COMMENTS ON REVIEWED SET. |
| | 11-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| | IN ORDER TO EXPEDITE THE REVIEW. |