| Plan Review Notes For Permit 01101896 |
| Permit Number |
01101896 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-11-21 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101896 | | | 2121 N DIXIE HWY | | | CONT: DAVID BIAGETTI | | | TEL: 436-9700 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- PERMIT APPLICATION ON FIRST REVIEW | | | WAS FOR "REMOVAL OF DOORS AND WINDOWS | | | AND TO REPLACE WITH BLOCK", THE SECOND | | | TIME IN ADDED "PLUMBING, ELEC & HVAC". | | | THERE IS NOTHING SAID ABOUT A PERMIT FOR | | | THE RECONSTRUCTION, EXTERIOR DOOR, AND | | | TWO OTHER OPENING OPENINGS THAT ARE NOT | | | INDICATED ON THE PLANWINDOW OR DOOR? | | | NOR DOES THE PERMIT APPLICATION SAY THIS | | | IS A TENANT BUILD OUT THOUGH THE PLANS | | | HAVE INTERIOR WALLS BATH ROOMS ETC! | | | NO MINIMUM BUILDING TYPE! | | | NO USAGE, OCCUPANCY! | | | NO ENERGY CALS! | | | NO PRODUCT APPROVALS FOR: | | | WINDOWS | | | DOORS | | | NO INFORMATION FOR INTERIOR FINISH | | | SCHEDULE | | | NO MINIMUM INTERIOR FINISH CLASSIFICA- | | | TION T 803.3 | | | SBC 1204.2 MISSING PUBLIC REST ROOM | | | NONABSORBANT MATERIALS ON FLOOR AND ON | | | WALLS TO A HEIGTH OF 4'-0". | | | PERMIT VALUE TO LOW FOR TYPE V RETAIL | | | VALUE 50% $44,460.00. |
|