| Notes |
| Date |
Text |
| 2001-11-20 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE 2 0F 2 SHOW 5' TURNING RADIUS IN | | | SHOWER BATH AS REQUIRED IN FACBC SEC | | | 4.2.3 | | | 2) PAGE 2 OF 2, SHOWER STALL. SHOW | | | COMPLIANCE WITH FACBC SEC 4.21. SHOW DE- | | | TAILS FOR SEC 4.21.1 THRU 4.21.8 | | | 3) PAGE 2 0F 2, SHOWER NOT SHOWN ON | | | SANITARY RISER DIAGRAM. | | | 4) PAGE 2 OF 2, PLUMBING NOTES #14. | | | AIR CHAMBERS ARE QUICK FIX AND REQUIRE | | | ACCESS PANEL AND VALVES TO RECHARGE PER | | | SPC 607.8.3 AND PDI-WH 201. APPROVED | | | WATER HAMMER ARRESTORS DO NOT REQUIRE | | | ACCESS AND SHALL BE SIZED AND LOCATED | | | PER MANUFACTURE INSTALLATION INSTRUCTION | | | AND PDI-WH 201. | | | 5) PAGE 2 0F 2, 2 COMPARTMENT STAINLESS | | | STEEL SINK. PLEASE INDICATE USAGE FOR | | | BLDG SO A DETERMINATION CAN BE MADE FOR | | | THE DRAINAGE SYSTEM FOR SINK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|