| 2002-04-19 00:00:00 | THE INFORMATION PROVIDED BY PROGRESSIVE |
| | DEVELOPMENT GROUP DATED 4/18/02 WAS |
| | REVIEWD WITH REGARDS TO THE |
| | CALCULATIONS FORM COMPUTERIZED |
| | STRUCTURAL DESIGN, INC., A COPY OF A |
| | REPORT FROM INTERTEK TESTING SERVICES |
| | FOR 1/4" LAMINATED GLASS TESTED TO |
| | Z97.1-1984 STAJNDARDS AND A PORTION OF |
| | A UL TEST REPORT FOR PHOTOVOLTAIC |
| | MODULES AND PANELS. |
| | |
| | THE PAID PLAN REVIEW FOR THIS PROJECT |
| | HAS BEEN COMPLETED.AS WAS NOTED IN |
| | THE EARLIER COMMENTS THE STATE OF |
| | FLORIDA INVOKED THE 2001 FLORIDA |
| | BUILDING CODE ON MARCH 1, 2002.THE |
| | GLASS SOLAR PANELS DID NOT COMPLY WITH |
| | THE PREVIOUS CODE IN EFFECT, 1997 |
| | SBCCI, NOR DO THEY MEET THE CURRENT |
| | 2001 FBC. |
| | |
| | A NEW REVIEW OR A PERMIT APPLICATION |
| | MUST BE APPLIED FOR THE ENTIRE PROJECT |
| | TO DETERMINE CONFORMANCE WITH THE 2001 |
| | FBC. |
| | |
| | THE GLAZED PANELS MUST BE DESIGNED TO |
| | COMPLY WITH FBC 2405.3.2.THE ENGINEER |
| | OF RECORD, OR A DELEGATED SPECIALTY |
| | ENGINEER MUST DEMONSTRATE COMPLIANCE |
| | WITH THIS REQUIREMENT.TO DATE THE |
| | GLAZING HASBEEN NOT INCLUDED IN THE |
| | CALCUALTIONS PROVIDED. |