2002-04-19 00:00:00THE INFORMATION PROVIDED BY PROGRESSIVE
 DEVELOPMENT GROUP DATED 4/18/02 WAS
 REVIEWD WITH REGARDS TO THE
 CALCULATIONS FORM COMPUTERIZED
 STRUCTURAL DESIGN, INC., A COPY OF A
 REPORT FROM INTERTEK TESTING SERVICES
 FOR 1/4" LAMINATED GLASS TESTED TO
 Z97.1-1984 STAJNDARDS AND A PORTION OF
 A UL TEST REPORT FOR PHOTOVOLTAIC
 MODULES AND PANELS.
  
 THE PAID PLAN REVIEW FOR THIS PROJECT
 HAS BEEN COMPLETED.AS WAS NOTED IN
 THE EARLIER COMMENTS THE STATE OF
 FLORIDA INVOKED THE 2001 FLORIDA
 BUILDING CODE ON MARCH 1, 2002.THE
 GLASS SOLAR PANELS DID NOT COMPLY WITH
 THE PREVIOUS CODE IN EFFECT, 1997
 SBCCI, NOR DO THEY MEET THE CURRENT
 2001 FBC.
  
 A NEW REVIEW OR A PERMIT APPLICATION
 MUST BE APPLIED FOR THE ENTIRE PROJECT
 TO DETERMINE CONFORMANCE WITH THE 2001
 FBC.
  
 THE GLAZED PANELS MUST BE DESIGNED TO
 COMPLY WITH FBC 2405.3.2.THE ENGINEER
 OF RECORD, OR A DELEGATED SPECIALTY
 ENGINEER MUST DEMONSTRATE COMPLIANCE
 WITH THIS REQUIREMENT.TO DATE THE
 GLAZING HASBEEN NOT INCLUDED IN THE
 CALCUALTIONS PROVIDED.