Plan Review Notes
Plan Review Notes For Permit 01101877
Permit Number 01101877
Review Stop E
Sequence Number 3
Notes
Date Text
2002-06-04 00:00:00************ REVISION/PROVISO*********
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 ON SUBMITTED SITE ELECTRICAL AND CANOPY
 PLANS UNDER OTHER PERMIT #`S (02051422,
 02051425) DO NOT CORRELATE WITH MAIN
 BLDG PLANS.
 2)NOTE: PLEASE NOTE THAT REVIEW IS DONE
 FOR E-SHEETS 1-4 ONLY. PLEASE NOTE THAT
 E-4 WILL CHANGE DUE TO CANOPY ELECTRICAL
  
 PLEASE VERFIY THE SETS CORRELATE IN
 FEILD FOR OTHER PERMITS.
 PLEASE SUBMIT A REVISED E-4 IF IS TO
 MATCH CANOPY PLANS.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372