2002-03-25 00:00:00BASED ON THE INFORMATION FROM
 PROGRESSIVE DEVELOPMENT DATED 3/18/02
 WHICH CONTAINS COPIES OF VARIOUS
 LETTERS, CUT SHEETS AND REPORTS, IT
 APPEARS THE "BP SOLAR PANELS" DO NOT
 COMPLY WITH FBC 2405.3.2.
  
 ASSUMING THE PANELS AS LAMINATED, HEAT
 STRENGHTED GLASS, THE ALLOWABLE LOAD
 WILL NOT COMPLY WHEN USING THE
 ENGINEER'S WINDLOAD CALCULATIONS
 PROVIDED THUS FAR.
  
 EFFECTIVE MARCH 1, 2002 THE FLORIDA
 LEGISLATURE MANDATED THE FLORIDA
 BUILDING CODE BE PLACED IN USE AND
 PERMITS APPLIED FOR SUBSEQUENT TO THAT
 DATE MUST COMPLY WITH THE FBC.TO DATE
 THIS PROJECT HAS BEENA PAID PLAN
 REVIEW AND NOT A PERMIT APPLICATION.
  
 WITH REGARDS TO WIND LOAD REQUIREMENTS
 THE ASCE 7-98 IS INVOKED BY THE FBC AND
 THE CITY OF WEST PALM BEACH IS LOCATED
 WITHIN THE 140 MPH WIND SPEED CONTOUR.
 PERHAPS A RE-ANALYSIS BY THE
 ENGINEER(S)FOR A 140 MPH ZONE RATHER
 THAN THE 150 MPH DECLARED IN THE
 CALCULATIONS WILL CHANGE THE FORCES
 SEEN BY THE SOLAR PANELS WHEN
 IVESTIGATED AS COMPONENTS AND CLADDING.