Plan Review Notes
Plan Review Notes For Permit 01101877
Permit Number 01101877
Review Stop B
Sequence Number 2
Notes
Date Text
2002-01-23 00:00:00THE HARMONY CANOPY DRAWING CS-1C SHEET 1
 OF 7 SIGNED AND SEALED BY ROGER
 LINGERFELTER, PE DECLARES WIND DESIGN
 TO ASCE 7-95, 140 MPH, EXPOSURE C.
  
 THE CALCULATIONS FROM COMPUTERIZED
 STRUCTURAL DESIGN, SC ARE NOT SIGNED
 AND SEALED BY A FL REGISTERED ENGINEER
 AND CITE DESIGN TO THE 1994 S. FL
 BUILDING CODE AND ASCE 7-88. FURTHER
 THE CALCULATIONS SPECIFICALLY EXCLUDE
 GLAZING,SOLAR PANELS AND FASCIA.
 ONLY THE ALUMINUM FRAME WORK IS COVERED.
  
 PROVIDE STRUCTURAL CALCULATIONS BY A FL
 REGISTERED PE, IN ACCORDANCE WITH ASCE
 7-95 THAT INCLUDES ALL OF THE
 COMPONENTS THAT WILL BE USED IN THE
 CANOPY.WHERE DESIGN IS BY A DELEGATED
 ENGINEER, THE DESIGN MUST BE REVIWED BY
 THE ENGINEER OF RECORD FOR CONFORMANCE
 WITH THE ORIGINAL DESIGN.SEE CHAPTER
 61G15-30, RESPONSIBILITY RULES COMMON
 TOALL ENGINEERS, OF THE FL
 ADMINISTRATIVE CODE.
  
 THE FASTENING METHOD FOR THE STEEL
 STORMPANELS ON NOA 99-0517.07 FOR
 ATTACHMENT TO CONCRETE IS ACCEPTABLE.
 THE ATTACHEDSHEETS COPIED FROM THE BP
 AMOCO DRAWINGS DEPICT ATTACHMENT TO
 SOMETHING OTHER THAN CONCRETE WITH AN
 UNDESIGNATED FASTENER SHOWING NEITHER
 LOCATION OR NUMBER.THIS IS NOT
 ACCEPTABLE.PLEASE PROVIDE A SIGNED
 AND SEALED METHOD DESIGNED IN
 ACCORDANCE WITH GOOD ENGINEERING
 PRACTICES IF THE ATTACHMENT IS TO
 DEVIATE FROM THAT SHOWN IN THE NOA.