Plan Review Notes
Plan Review Notes For Permit 01101877
Permit Number 01101877
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-11-27 00:00:001) NO ITEMS TO BE PLACED WITHIN 18 FEET
 OF THE FIRE HYDRANT SHOWN ON THE PLAN.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR UNDERGROUND FUEL TANKS.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD,DUCT,AND EXTINGUISHING
 SYSTEMS.
 4) PLEASE PROVIDE FLAME SPREAD CRITERIA
 FOR CANOPY LOCATED OVER FUEL PUMPS.
 5) EMERGENCY CONTROLS FOR FUEL PUMPS
 ARE NOT TO EXCEED 100 FEET.
 6) PLEASE PROVIDE DETAILS ON ALL FUEL
 PUMPS PLANNED FOR USE. ALL EQUIPMENT IS
 TO BE LISTED AND BE EQUIPPED WITH
 LISTED BREAKWAY DEVICES, APPROVED
 NOZZLES, AND APPROVED FUEL HOSES THAT
 DO NOT EXCEED 18 FEET IN LENGTH.
 7) UNDERGROUND FUEL TANKS ARE TO BE
 INSTALLED A MINIMUM OF 5 FEET FROM
 PROPERTY LINES.
 8) IT WILL DEPEND ON WHEN THE PLANS ARE
 OFFICIALLY PERMITTED AS TO WHAT THE
 APPLICABLE FIRE CODE WILL BE. JANUARY
 1, 2002, THE FLORIDA FIRE PREVENTION
 CODE WILL BE IN EFFECT, WHICH INVOKES
 THE 2000 LIFE SAFETY CODE.
 9) FLAME SPREAD DETAILS NEEDED ON
 CANOPY OVER FUEL PUMPS.
 10) PLEASE EXPLAIN PROPANE TANKS LOCATED
 NEAR EXIT DOOR.
 11) ANY POWER OPERATED DOORS ARE TO
 MEET LIFE SAFETY CODE REQUIREMENTS.
 12) PLEASE INDICATE ALL LOCATIONS OF
 WARNING SIGNS, AND THEIR VERBAGE.
 13) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILING OF
 STORE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910