| 2001-11-27 00:00:00 | 1) NO ITEMS TO BE PLACED WITHIN 18 FEET |
| | OF THE FIRE HYDRANT SHOWN ON THE PLAN. |
| | 2) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR UNDERGROUND FUEL TANKS. |
| | 3) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR ANY HOOD,DUCT,AND EXTINGUISHING |
| | SYSTEMS. |
| | 4) PLEASE PROVIDE FLAME SPREAD CRITERIA |
| | FOR CANOPY LOCATED OVER FUEL PUMPS. |
| | 5) EMERGENCY CONTROLS FOR FUEL PUMPS |
| | ARE NOT TO EXCEED 100 FEET. |
| | 6) PLEASE PROVIDE DETAILS ON ALL FUEL |
| | PUMPS PLANNED FOR USE. ALL EQUIPMENT IS |
| | TO BE LISTED AND BE EQUIPPED WITH |
| | LISTED BREAKWAY DEVICES, APPROVED |
| | NOZZLES, AND APPROVED FUEL HOSES THAT |
| | DO NOT EXCEED 18 FEET IN LENGTH. |
| | 7) UNDERGROUND FUEL TANKS ARE TO BE |
| | INSTALLED A MINIMUM OF 5 FEET FROM |
| | PROPERTY LINES. |
| | 8) IT WILL DEPEND ON WHEN THE PLANS ARE |
| | OFFICIALLY PERMITTED AS TO WHAT THE |
| | APPLICABLE FIRE CODE WILL BE. JANUARY |
| | 1, 2002, THE FLORIDA FIRE PREVENTION |
| | CODE WILL BE IN EFFECT, WHICH INVOKES |
| | THE 2000 LIFE SAFETY CODE. |
| | 9) FLAME SPREAD DETAILS NEEDED ON |
| | CANOPY OVER FUEL PUMPS. |
| | 10) PLEASE EXPLAIN PROPANE TANKS LOCATED |
| | NEAR EXIT DOOR. |
| | 11) ANY POWER OPERATED DOORS ARE TO |
| | MEET LIFE SAFETY CODE REQUIREMENTS. |
| | 12) PLEASE INDICATE ALL LOCATIONS OF |
| | WARNING SIGNS, AND THEIR VERBAGE. |
| | 13) PLEASE PROVIDE INTERIOR FINISH |
| | INFORMATION FOR WALLS AND CEILING OF |
| | STORE. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |