Plan Review Notes
Plan Review Notes For Permit 01101877
Permit Number 01101877
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-11-21 00:00:00FAILED :
 SHEET 2, PAVING & GRADING NOTES;
 NOTE # 8 , ALL OFF-STREET PARKING STALL
 MUST BE STRIPED WITH DOUBLE 4" PAINTED
 STRIPES PER CITY OF WPB.PLEASE REVISED
 DETAILS ON SHEET 12.
 SHEET 2, SANITARY SEWER NOTES;
 NOTE # 8, ALL DUCTILE IRON PIPES USED
 FOR GRAVITY MAIN MUST BE A MIN. OF CLASS
 51, PLEASE VERIFY.
 NOTE # 3, ALL SANITARY SEWER MAIN AND
 SERVICE LATERALS SHALL BE CONSTRUCTED OF
 PVC PIPE WITH RING-TITE JOINTS , ASTM
 D-3034-SDR 26.
 NOTE # 6, PVC SEWER FITTING SHALL
 CONFORM TO THE REQUIREMENT OF ASTM
 D-3034 STANDARD WITH MIN. WALL THICKNESS
 OF SDR26.
 ALL BACKFLOW PREVENTERS MUST BE APPROVED
 BY PUBLIC UTILITIES DEPT. CITY OF WPB
 659-8040.
 A SEPARATE PERMIT AND APPROVAL FROM
 PUBLIC UTILITIES DEPT. FOR ALL NEW
 CONNECTIONS IS REQUIRED,659-8040.
 CONTRACTOR TO CONTACT RODNEY COMPO FOR
 INSTALLATION/ INSPECTION OF GREASE TRAP,
 837-4051 EXT. 4074.
 ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE APPROVAL AND PERMIT FROM CITY
 ENGINEER'S OFFICE, 659-8040.
 SEPARATE PERMIT FOR UNDERGROUND
 UTILITIES/SITE WORKS IS RECOMMENDED AT
 THE TIME OF ACTUAL PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI