| Plan Review Notes For Permit 01101877 |
| Permit Number |
01101877 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-11-26 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: NOTE THAT OUTLET SPACING NEEDS | | | TO MEET LOCAL CODE. SEEMS WALLS ALONG | | | FRONT WILL BE MISSING A COUPLE. | | | EVERY 20' OF WALL/FIXED PANEL SPACE. | | | PER 210-50 OF CITY-WIDE AMENDMENTS. | | | | | | 2)NOTE: PLEASE NOTE THAT FOOTER STEEL IS | | | TO BE PART OF THE GROUNDING ELECTRODE | | | SYSTEM PER 250-50. | | | | | | 3)NOTE: PLEASE CLARIFY THE CONDUIT SIZE | | | FOR FEEDS TO MDP. | | | ONE-LINE SHOWS 4" AND THE CONDUIT SCHED- | | | -ULE SHOWS 3 1/2". | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|